Commissioning

6.3 LCP Menu

For more detailed instructions regarding the menus or
parameters, refer to the programming guide.
6.3.1.1 Quick Menu Mode
The LCP provides access to parameters via the Quick
Menus. To list the quick menu options, press [Quick
Menus].
0.0%
0.00
Quick Menus
01 My Personal Menu
02 Quick Setup
03 Function Setups
04 Smart Start
05 Changes Made
06 Loggings
07 Water and Pumps
Illustration 6.1 Quick Menu View
6.3.1.2 Q1 My Personal Menu
The Personal Menu is used to determine what is shown in
the display area. Refer to chapter 3.6 Local Control Panel
(LCP). This menu can also show up to 50 pre-programmed
parameters. These 50 parameters are manually entered
using parameter 0-25 My Personal Menu.
6.3.1.3 Q2 Quick Setup
The parameters found in the Q2 Quick Setup contain basic
system and motor data that are always necessary for
configuring the drive. See chapter 6.4.2 Entering System
Information for the set-up procedures.
6.3.1.4 Q3 Function Setups
The parameters found in the Q3 Function Setups contain
data for fan, compressor, and pump functions. This menu
also includes parameters for LCP display, digital preset
speeds, scaling of analog references, closed-loop single
zone, and multizone applications.
6.3.1.5 Q4 Smart Start
The Q4 Smart Start function prompts the user for questions
based on the previous answer which, in turn, automatically
configures the motor and selected pump/fan/conveyor
application.
MG22A102
Operating Guide
6.3.1.6 Q5 Changes Made
Select Q5 Changes Made for information about:
6.3.1.7 Q6 Loggings
Use Q6 Loggings for fault finding. To get information about
the display line readout, select Loggings. The information is
shown as graphs. Only parameters selected in
1(1)
parameter 0-20 Display Line 1.1 Small through
parameter 0-24 Display Line 3 Large can be viewed. It is
possible to store up to 120 samples in the memory for
later reference.
Q6 Loggings
Parameter 0-20 Display Line 1.1 Small
Parameter 0-21 Display Line 1.2 Small
Parameter 0-22 Display Line 1.3 Small
Parameter 0-23 Display Line 2 Large
Parameter 0-24 Display Line 3 Large
Table 6.1 Logging Parameter Examples
6.3.1.8 Q7 Water and Pumps
The parameters found in the Q7 Water and Pumps contain
basic data that is necessary for configuring water pump
applications.
6.3.1.9 Main Menu Mode
The LCP provides access to the Main Menu mode. Select
the Main Menu mode by pressing the [Main Menu] key.
The resulting readout appears on the LCP display.
18.4%
Main Menu
Keypad Set-Up
Parameter Data Set
Parameter Data Check
Drive Information
07 Motor Setup
Illustration 6.2 Main Menu View
Lines 2 through 5 on the display show a list of parameter
groups that can be selected via the [
All parameters can be changed in the main menu. Option
cards added to the unit enable extra parameters associated
with the option device.
Danfoss A/S © 01/2017 All rights reserved.
The 10 most recent changes.
Changes made from default setting.
5.22A
] and [
6
Reference [Unit]
Analog Input 53 [V]
Motor current [A]
Frequency [Hz]
Feedback [Unit]
1(1)
] keys.
47
6