Danfoss VLT AQUA Drive FC 202 Operating Manual page 46

355–800 kw enclosure size e
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Electrical Installation
5.8.10 Selecting Voltage/Current Input
Signal
The analog input terminals 53 and 54 allow setting of
input signal to voltage (0–10 V) or current (0/4–20 mA).
Default parameter setting:
Terminal 53: Speed reference signal in open loop
(see parameter 16-61 Terminal 53 Switch Setting).
Terminal 54: Feedback signal in closed loop (see
parameter 16-63 Terminal 54 Switch Setting).
5
5
NOTICE
Disconnect power to the drive before changing switch
positions.
1.
Remove the LCP (local control panel).
See chapter 6.3 LCP Menu.
2.
Remove any optional equipment covering the
switches.
3.
Set switches A53 and A54 to select the signal
type (U = voltage, I = current).
Illustration 5.22 Location of Terminal 53 and 54 Switches
44
VLT® AQUA Drive FC 202
Danfoss A/S © 01/2017 All rights reserved.
MG22A102

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt refrigeration drive fc 103

Table of Contents