Danfoss VLT AQUA Drive FC 202 Operating Manual page 78

355–800 kw enclosure size e
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
FC 202
High/normal load
(High overload=150% current during 60 s, normal
overload=110% current during 60 s)
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 550 V) [A]
Intermittent (60 s overload) (at 550 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/690 V) [A]
Continuous kVA (at 550 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 550 V) [A]
Continuous (at 575 V) [A]
Continuous (at 690 V) [A]
Maximum number and size of cables
per phase (E1h)
- Mains and motor without brake [mm
9
9
- Mains and motor with brake [mm
- Brake or regeneration [mm
Maximum number and size of cables
per phase (E3h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
- Load share or regeneration [mm
Maximum external mains fuses [A]
Estimated power loss at 600 V [W]
Estimated power loss at 690 V [W]
Efficiency
4)
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Power card overtemperature trip [°C (°F)]
Fan power card overtemperature trip [°C (°F)]
Active in-rush card overtemperature trip [°C (°F)]
Table 9.4 Technical Specifications, Mains Supply 3x525–690 V AC
76
VLT® AQUA Drive FC 202
2
1)
(AWG)]
2
(AWG)
1)
2
(AWG)
1)
2
(AWG)]
1)
2
1)
(AWG)
2
1)
(AWG)
2)
3)4)
3)4)
Danfoss A/S © 01/2017 All rights reserved.
N560
HO
NO
400
450
500
600
500
560
E1h/E3h
523
596
785
656
500
570
750
627
498
568
498
568
598
681
504
574
482
549
482
549
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
6493
7395
6707
7653
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
N630
HO
NO
450
500
600
650
560
630
E1h/E3h
596
630
894
693
570
630
855
693
568
600
568
627
681
753
574
607
549
607
549
607
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
7383
8209
7633
8495
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
MG22A102

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt refrigeration drive fc 103

Table of Contents