9.7 Fuses

Fuses ensure that possible damage to the drive is limited to damages inside the unit. To ensure compliance with EN 50178,
use identical Bussmann fuses as replacements. Refer to Table 9.6.
NOTICE
Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations.
Input voltage (V)
380–500
9
9
525–690
Table 9.6 Fuse Options
The fuses listed in Table 9.6 are suitable for use on a circuit capable of delivering 100000 A
the drive voltage rating. With the proper fusing, the drive short-circuit current rating (SCCR) is 100000 A
drives are supplied with internal drive fusing to meet the 100 kA SCCR. E3h and E4h drives must be fitted with Type aR
fuses to meet the 100 kA SCCR.
NOTICE
DISCONNECT SWITCH
All units ordered and supplied with a factory-installed disconnect switch require Class L branch circuit fusing to meet
the 100 kA SCCR for the drive. If a circuit breaker is used, the SCCR rating is 42 kA. The specific Class L fuse is
determined by the input voltage and power rating of the drive. The input voltage and power rating is found on the
product nameplate. See chapter 4.1 Items Supplied.
Input voltage (V)
380–480
380–480
525–690
525–690
82
VLT® AQUA Drive FC 202
Bussmann part number
170M7309
170M7342
Power rating (kW)
Short circuit rating (A)
355–450
42000
100000
500–560
42000
100000
450–630
42000
10000
710–800
42000
100000
Danfoss A/S © 01/2017 All rights reserved.
1.1 (full speed)
USB type B device plug
(symmetrical), depending on
rms
. E1h and E2h
rms
Required protection
Circuit breaker
Class L fuse, 800 A
Circuit breaker
Class L fuse, 1200 A
Circuit breaker
Class L fuse, 800 A
Circuit breaker
Class L fuse, 1200 A
5 ms
MG22A102