Specifications
FC 202
High/normal load
(High overload=150% current during 60 s, normal
overload=110% current during 60 s)
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 550 V) [A]
Intermittent (60 s overload) (at 550 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/690 V) [A]
Continuous kVA (at 550 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 550 V) [A]
Continuous (at 575 V) [A]
Continuous (at 690 V) [A]
Maximum number and size of cables
per phase (E2h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
- Brake or regeneration [mm
2
(AWG)
Maximum number and size of cables
per phase (E4h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
- Load share or regeneration [mm
Maximum external mains fuses [A]
Estimated power loss at 600 V [W]
Estimated power loss at 690 V [W]
Efficiency
4)
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Power card overtemperature trip [°C (°F)]
Fan power card overtemperature trip [°C (°F)]
Active in-rush card overtemperature trip [°C (°F)]
Table 9.5 Technical Specifications, Mains Supply 3x525–690 V AC
1) American Wire Gauge.
2) For fuse ratings, see chapter 9.7 Fuses.
3) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and
customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
4) Measured using 5 m shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency
class, see chapter 9.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency.
MG22A102
Operating Guide
2
1)
(AWG)]
2
(AWG)
1)
1)
2
(AWG)]
1)
2
1)
(AWG)
2
1)
(AWG)
2)
3) 4)
3) 4)
Danfoss A/S © 01/2017 All rights reserved.
N710
HO
NO
500
560
650
750
630
710
E2h/E4h
659
763
989
839
630
730
945
803
628
727
627
727
753
872
642
743
613
711
613
711
6x240 (6x500 mcm)
5x240 (5x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
1200
8075
9500
8388
9863
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
± 15% (tolerance relates to variety in voltage and cable conditions.) These
N800
HO
NO
560
670
750
950
710
800
E2h/E4h
763
889
1145
978
730
850
1095
935
727
847
727
847
872
1016
743
866
711
828
711
828
6x240 (6x500 mcm)
5x240 (5x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
1200
9165
10872
9537
11304
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
77
9
9