Mechanical Installation
Illustration 4.2 Recommended Lifting Method

4.7 E1h/E2h Mechanical Installation

The E1h and E2h enclosure size is intended only for floor
installation, and is shipped with a pedestal and a gland
plate. The pedestal and gland plate must be installed for
proper installation.
The pedestal is 200 mm (7.9 in) and has an opening in the
front to allow airflow necessary to cool the power
components of the drive.
The gland plate is necessary to provide cooling air to the
control components of the drive via the door fan, and to
maintain the IP21/Type 1 or IP54/Type 12 protection rating.
4.7.1 Securing the Pedestal to the Floor
The pedestal must be secured to the floor using 6 bolts
before installing the enclosure.
1.
Determine proper placement of the unit,
concerning operating conditions and cable
access.
2.
Access the mounting holes by removing the front
panel of the pedestal.
3.
Set the pedestal on the floor and secure using 6
bolts through the mounting holes. Refer to the
circled areas in Illustration 4.3.
MG22A102
Operating Guide
Illustration 4.3 Pedestal to Floor Mounting Points
4.7.2 Attaching the E1h/E2h to the Pedestal
1.
2.
3.
4.
5.
6.
Danfoss A/S © 01/2017 All rights reserved.
Lift the drive and position it on the pedestal.
There are 2 bolts in the rear of the pedestal that
slide into the 2 slotted holes in the rear of the
enclosure. Position the drive by adjusting the
bolts up or down. Loosely secure with 2 M10 nuts
and locking brackets. See Illustration 4.4.
Verify that there is 225 mm (9 in) top clearance
for air exhaust.
Verify that the air intake at the bottom front of
the unit is not obstructed.
Around the top of the pedestal, secure the
enclosure using 6 M10x30 fasteners. Refer to
Illustration 4.5. Loosely tighten each bolt until all
bolts are installed.
Fasten each bolt securely and torque to 19 Nm
(169 in-lb).
Torque the 2 M10 nuts at the rear of the
enclosure to 19 Nm (169 in-lb).