Commissioning
Parameter 14-22 Operation Mode does not reset settings
such as the following:
Running hours
Serial communication options
Personal menu settings
Fault log, alarm log, and other monitoring
functions
Recommended initialization
1.
Press [Main Menu] twice to access parameters.
2.
Go to parameter 14-22 Operation Mode and
press [OK].
3.
Scroll to Initialization and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit. Default parameter
settings are restored during start-up. Start-up
takes slightly longer than normal.
6.
After alarm 80, Drive initialized to default value
appears, press [Reset].
Manual initialization
Manual initialization resets all factory settings except for
the following:
Parameter 15-00 Operating hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
To perform manual initialization:
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK]
simultaneously while applying power to the unit
(approximately 5 s or until an audible click
sounds and the fan starts). Start-up takes slightly
longer than normal.