Endress+Hauser Proservo NMS5 Operating Instructions Manual page 73

Hide thumbs Also See for Proservo NMS5:
Table of Contents

Advertisement

Proservo NMS5
Endress+Hauser
G8V4H6 LIQ. WAIT TIME
Item
Matrix Group : TANK PROFILE
Function
Group
GVH=846
TANK
LIQ. WAIT
PROFILE
TIME
Figure. 73: G8V4H6
G8V4H7 OPE. WAIT TIME
Item
Matrix Group : TANK PROFILE
Function
Group
TANK
PROFILE
Figure. 74: G8V4H7
Procedure
1.
Select G8V4H6 "LIQ.
WAIT TIME" to
determine the displacer
weight calibration
interval between each
measuring point in the
liquid.
2.
Enter desired waiting
time by pressing + or -
key, and select E to
enter.
Procedure
1.
Select G8V4H7 "OPE.
WAIT TIME" to
determine the operation
holding time limit to
accept "BAL. LEVEL"
GVH=847
before the actual
OPE. WAIT
TIME
operation starts.
2.
Enter desired waiting
time by pressing + or -
key, and select E to
enter.
7 Commissioning
Remarks
• Set access code to 51. A
small turbulence made by
the movement of displacer
itself may cause the liquid
surrounding displacer to be
unstable for the accurate
measurement.
• This function allows
displacer to hold in each
calculated position before
actual measurement is
proceeded based on the
entered value.
Remarks
• Set access code to 51.
Entire operation begins
only when the condition
described in "BAL. LEVEL"
is achieved.
• This function determines
how long for the NMS to
wait if "BAL. LEVEL" can
not be established before
quitting entire operation.
73