Technical data
10.5 Information on insulation, protection class, degree of protection and rated voltage
Climatic ambient conditions
You may use the CPU 1515SP PC (F) under the following climatic, ambient conditions.
Table 10- 10 Climatic ambient conditions
Ambient conditions
Temperature:
Horizontal mounting position:
Vertical installation:
Permitted temperature change
Relative humidity
Barometric pressure
Concentration of pollutants
10.5
Information on insulation, protection class, degree of protection and
rated voltage
Insulation
The insulation is designed according to the requirements of EN 61131-2: 2007.
Note
For modules with 24 V DC supply voltage, the electrical isolation is designed for max. 60 V
AC / 75 V DC and basic insulation is designed according to EN 61131-2: 2007.
Pollution degree/overvoltage category according to IEC 61131
● Pollution degree 2
● Overvoltage category: II
110
Permissible range
from 0 to 60 °C
•
from 0 to 55 °C
•
0 to 50 °C
•
10 K/h
from 10 to 95%
1080 hPa to 795 hPa
SO
: <0.5 ppm;
2
RH <60 %, no condensation
H
S: <0.1 ppm;
2
RH <60 %, no condensation
ISA-S71.04 severity level G1; G2; G3
Comments
For configuration with 32 I/O modules and 3 x
100 mA USB load
For configuration with 64 I/O modules and 2 x
500 mA + 1 x 100 mA USB load
For configuration with 32 I/O modules and 3 x
100 mA USB load
-
Without condensation, corresponds to rela-
tive humidity (RH) class 2 according to IEC
61131 part 2
Corresponds to an altitude of -1000 m
to 2000 m
-
-
Manual, 05/2017, A5E32701806-AC
CPU 1515SP PC (F)