YASKAWA SGDV User Manual page 33

Ac servo drives. e-v series. rotational motor
Hide thumbs Also See for SGDV:
Table of Contents

Advertisement

2 Installation
2.3.2 Installation Standards
• Inside the Control Panel
The conditions inside the control panel should be the same as the environmental con-
ditions of the SERVOPACK. Refer to 2.1.2 SERVOPACK Installation Environment.
The SGDV-
(Un022). With this monitor, operation conditions in the installation environment can
be observed and measured.
The value shown on this monitor should be equal to or less than 100% for optimum
operating conditions.
If this value is over 100%, one of the following measures must be taken to ensure
safe operation and a long product life.
Improve air circulation around SERVOPACKs.
Minimum Air Circulation Rate
Top (10 mm): 0.5 m/s
Bottom (10 mm): 0.2 m/s
To improve the air circulation to meet these minimum standards and to lower the per-
centage shown on the monitor, widen the space between the SERVOPACKs or lower
the temperature of the surrounding air.
<Note>
For every increase of 10°C, the percentage shown on the monitor will also increase
by approximately ten.
2-12
B SERVOPACKs have an Installation Environment monitor

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SgmavSgmjvSgmsvSgmpsSgmgv

Table of Contents