2.4 SPECIFICATIONS
OSCILLOGRAPHY
Maximum records:
Sampling rate:
Triggers:
2
Data:
Data storage:
EVENT RECORDER
Capacity:
Time-tag:
Triggers:
Data storage:
DATA LOGGER
Number of channels:
Parameters:
Sampling rate:
Trigger:
Mode:
Storage capacity:
RMS CURRENT: PHASE, NEUTRAL, AND GROUND
Accuracy at
0.1 to 2.0 × CT rating: ±0.25% of reading or ±0.1% of rated
> 2.0 × CT rating:
RMS VOLTAGE
Accuracy:
REAL POWER (WATTS)
Accuracy at 0.1 to 1.5 x
CT rating and 0.8 to
1.2 x VT rating:
2-22
64
64 samples per power cycle
any element pickup, dropout, or operate;
contact input change of state; contact
output change of state; FlexLogic equa-
tion
AC input channels; element state; con-
tact input state; contact output state
in non-volatile memory
1024 events
to 1 microsecond
any element pickup, dropout, or operate;
contact input change of state; contact
output change of state; self-test events
in non-volatile memory
1 to 16
any available analog actual value
15 to 3600000 ms in steps of 1
any FlexLogic operand
continuous or triggered
(NN is dependent on memory)
1-second rate:
01 channel for NN days
16 channels for NN days
60-minute rate:
01 channel for NN days
16 channels for NN days
(whichever is greater)
±1.0% of reading
±0.5% of reading from 10 to 208 V
±1.0% of reading at –1.0 ≤ PF< –0.8 and
0.8 < PF ≤ 10
C60 Breaker Protection System
2 PRODUCT DESCRIPTION
FAULT LOCATOR
Method:
single-ended
Voltage source:
wye-connected VTs, delta-connected
VTs and neutral voltage, delta-connected
VTs and zero-sequence current (approxi-
mation)
Maximum accuracy if:
fault resistance is zero or fault currents
from all line terminals are in phase
Relay accuracy:
±1.5% (V > 10 V, I > 0.1 pu)
Worst-case accuracy:
VT
+
user data
%error
CT
+
user data
%error
Z
+
user data
Line%error
METHOD
+
see chapter 8
%error
RELAY ACCURACY
+ (1.5%)
%error
PHASOR MEASUREMENT UNIT
Output format:
per IEEE C37.118 or IEC 61850-90-5
standard
Number of channels:
14 synchrophasors, 8 analogs, 16 digi-
tals
TVE (total vector error)
<1%
Triggering:
frequency, voltage, current, power, rate
of change of frequency, user-defined
Reporting rate:
1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60
times per second for P and M class, and
100 or 120 times per second for P class
only
Number of clients:
One over TCP/IP port and one over
UDP/IP per aggregator
AC ranges:
As indicated in appropriate specifications
sections
Network reporting format: 16-bit integer (for IEEE C37.118) or 32-
bit IEEE floating point numbers
Network reporting style: rectangular (real and imaginary for IEEE
C37.188) or polar (magnitude and angle)
coordinates
Post-filtering:
none, 3-point, 5-point, 7-point
Calibration:±5° (angle) and ±5% (magnitude)
REACTIVE POWER (VARS)
Accuracy at 0.1 to 1.5 x
CT rating and 0.8 to
1.2 x VT rating:
±1.0% of reading at –0.2 ≤ PF ≤ 0.2
APPARENT POWER (VA)
Accuracy at 0.1 to 1.5 x
CT rating and 0.8 to
1.2 x VT rating:
±1.0% of reading
WATT-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
±2.0% of reading
±0 to 1 × 10
Range:
Parameters:
three-phase only
Update rate:
50 ms

2.4.3 MONITORING

2.4.4 METERING

6
MWh
GE Multilin