GE C60 Instruction Manual page 534

Breaker protection system ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 34 of 66)
ADDR
REGISTER NAME
6894
Autoreclose Mode Aut
6895
Autoreclose Mode 1 Activation
6897
Autoreclose Mode 2 Activation
6899
Autoreclose Mode 3 Activation
B
689B
Autoreclose Mode 4 Activation
Phase Undervoltage (Read/Write Grouped Setting) (3 modules)
7000
Phase Undervoltage 1 Function
7001
Phase Undervoltage 1 Signal Source
7002
Phase Undervoltage 1 Pickup
7003
Phase Undervoltage 1 Curve
7004
Phase Undervoltage 1 Delay
7005
Phase Undervoltage 1 Minimum Voltage
7006
Phase Undervoltage 1 Block
7008
Phase Undervoltage 1 Target
7009
Phase Undervoltage 1 Events
700A
Phase Undervoltage 1 Measurement Mode
700B
Reserved (6 items)
7011
...Repeated for Phase Undervoltage 2
7022
...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting) (3 modules)
7040
Phase Overvoltage 1 Function
7041
Phase Overvoltage 1 Source
7042
Phase Overvoltage 1 Pickup
7043
Phase Overvoltage 1 Delay
7044
Phase Overvoltage 1 Reset Delay
7045
Phase Overvoltage 1 Block
7047
Phase Overvoltage 1 Target
7048
Phase Overvoltage 1 Events
7049
...Repeated for Phase Overvoltage 2
7052
...Repeated for Phase Overvoltage 3
Breaker Arcing Current Settings (Read/Write Setting) (4 modules)
7290
Breaker 1 Arcing Amp Function
7291
Breaker 1 Arcing Amp Source
7292
Breaker 1 Arcing Amp Init
7294
Breaker 1 Arcing Amp Init B
7296
Breaker 1 Arcing Amp Init C
7298
Breaker 1 Arcing Amp Delay
7299
Breaker 1 Arcing Amp Limit
729A
Breaker 1 Arcing Amp Block
729C
Breaker 1 Arcing Amp Target
729D
Breaker 1 Arcing Amp Events
729E
...Repeated for Breaker 2 Arcing Amp
72AC
...Repeated for Breaker 3 Arcing Amp
72BA
...Repeated for Breaker 4 Arcing Amp
Disconnect (Breaker) Switch (Read/Write Setting) (16 modules)
74A0
Disconnect Switch 1 Function
74A1
Disconnect Switch 1 Name
74A4
Disconnect Switch 1 Mode
74A5
Disconnect Switch 1 Open
74A7
Disconnect Switch 1 Block Open
74A9
Disconnect Switch 1 Close
74AB
Disconnect Switch 1 Block Close
74AD
Disconnect Switch 1 Phase A / Three-pole Closed
B-42
RANGE
0 to 3
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 5
0 to 3
0 to 1
0 to 600
0 to 3
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 5
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 50000
0 to 4294967295
0 to 2
0 to 1
0 to 1
---
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
C60 Breaker Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F622
0 (Mode 1 (1 & 3
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F167
pu
0.001
F001
---
1
F111
0 (Definite Time)
s
0.01
F001
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F186
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F167
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
kA2-cyc
1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
DEFAULT
Pole))
0
0
0
0
0 (Disabled)
0 (SRC 1)
1000
100
100
0
0 (Self-reset)
0 (Disabled)
0 (Phase to
Ground)
0
0 (Disabled)
0 (SRC 1)
1000
100
100
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0 (SRC 1)
0
0
0
0
1000
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
"SW 1"
0 (3-Pole)
0
0
0
0
0
GE Multilin