5 SETTINGS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 COMMUNICATIONS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
b) SERIAL PORTS
PATH: SETTINGS
PRODUCT SETUP
 SERIAL PORTS
MESSAGE
MESSAGE
and
RS485 COM2 BAUD RATE
PARITY
RS232 port is intended for local use and is fixed at 19200 bit/s baud and even parity. The rear COM2 port is RS485 and has
settings for baud rate and parity. It is important that these parameters agree with the settings used on the computer or other
equipment that is connected to these ports. Any of these ports can be connected to a computer running EnerVista UR
Setup. This software can download and upload setting files, view measured parameters, and upgrade the relay firmware. A
maximum of 32 relays can be daisy-chained and connected to a DCS, PLC, or computer using the RS485 ports. If IEC
60870-103 is chosen as the protocol, valid baud rates are 9600 and 19200 bit/s, and valid parity is Even.
GE Multilin


COMMUNICATIONS

 SERIAL PORTS
 NETWORK
 ROUTING
 MODBUS PROTOCOL
PROTOCOL:
DNP 3.0
 DNP PROTOCOL
 DNP / IEC 104
 POINT LISTS
 IEC 61850 PROTOCOL
 WEB SERVER
 HTTP PROTOCOL
 TFTP PROTOCOL
 IEC 60870-5-104
 PROTOCOL
 EGD PROTOCOL
 IEC103
 PROTOCOL

COMMUNICATIONS
SERIAL PORTS
RS485 COM2 BAUD RATE:
19200
RS485 COM2 PARITY:
Even
RS485 COM2 RESPONSE
MIN TIME:
0 ms
: The C60 is equipped with two independent serial communication ports. The faceplate
C60 Breaker Protection System
5.2 PRODUCT SETUP
5.2.4 COMMUNICATIONS
See page 5–27.
See page 5–30.
See page 5–32.
See page 5–35.
Range: DNP 3.0, IEC 60870-5-104, IEC 60870-5-103
See page 5–37.
See page 5–40.
See page 5–41.
See page 5–56.
See page 5–56.
See page 5–57.
See page 5–58.
See page 5–60.
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200 bit/s
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10