GE C60 Instruction Manual page 197

Breaker protection system ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

5 SETTINGS
 POINT 0
MESSAGE
MESSAGE
 POINT 95
MESSAGE
MESSAGE
The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binary
inputs (points) can be mapped this way.
The IEC60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 point
list must be in a continuous block, any points assigned after the first "Off" point are ignored.
For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form the
Information Object Identifier field of the ASDU, as defined in IEC60870-5-103.
The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation received
from the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.
If the C60 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the con-
trol field of the response).
For any change to take effect, restart the relay.
PATH: SETTINGS
PRODUCT SETUP
 IEC103 INPUTS
 MEASURANDS
MESSAGE
MESSAGE
MESSAGE
GE Multilin
POINT 0 FUN
0
POINT 0 INF
0
POINT 0 Input
Off
POINT 95 FUN
0
POINT 95 INF
0
POINT 95 Input
Off


COMMUNICATIONS
IEC60870-5-103
 ASDU 1
 ASDU 2
 ASDU 3
 ASDU 4
C60 Breaker Protection System
5.2 PRODUCT SETUP
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: FlexLogic operand
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: FlexLogic operand
IEC103 INPUTS MEASURANDS
Range: see sub-menu below
Range: see sub-menu below
Range: see sub-menu below
Range: see sub-menu below
5
5-61