GE C60 Instruction Manual page 162

Breaker protection system ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programma-
ble pushbuttons to clear specific records are typical applications for these commands. Since the C60 responds to rising
edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-program-
mable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programma-
ble pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, the following settings should be applied.
1.
Assign the clear demand function to pushbutton 1 by making the following change in the

CLEAR RELAY RECORDS
CLEAR DEMAND:
2.
Set the properties for user-programmable pushbutton 1 by making the following changes in the

SETUP
USER-PROGRAMMABLE PUSHBUTTONS
5
PUSHBUTTON 1 FUNCTION:
PUSHBTN 1 DROP-OUT TIME:
5-26
CLEAR DEMAND:
MESSAGE
Off
CLEAR ENERGY:
MESSAGE
Off
RESET UNAUTH ACCESS:
MESSAGE
Off
CLEAR DIR I/O STATS:
MESSAGE
Off
menu:
"
"
PUSHBUTTON 1 ON
"Self-reset"
"0.20 s"
C60 Breaker Protection System
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand.
Valid only for units with Direct I/O module.
menu:
USER PUSHBUTTON 1
5 SETTINGS
SETTINGS
PRODUCT SETUP
SETTINGS
PRODUCT
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents