5 SETTINGS
Modification of SYNC Word in CFG-2 for TR 90-5 Data Sets
In the CFG-2 file, all relevant information about the data being streamed is included. However, this file does not include the
fact that it describes a 90-5 dataset or the number of Application Service Data Units (datasets). In order to communicate
this information via the CFG-2 file for a given aggregator, when the aggregator is set to 90-5, the version number of the
CFG-2 file (found in bits 0-3 of the frame SYNC word, which should presently be set to 2) is set as follows:
VALUE
(DECIMAL)
# OF ASDUS
11
1
12
2
13
3
14
4
The PMU settings are organized in logical groups as follows. For correct PMU operation, upgrade the firmware to the latest
v7.2x release; consult the v7.2x Release Notes for information.

ATH: SETTINGS
SYSTEM SETUP
 PHASOR MEASUREMENT
 UNIT 1
MESSAGE
MESSAGE
MESSAGE
GE Multilin

PHASOR MEASUREMENT UNIT
 PMU 1 BASIC
 CONFIGURATION
 PMU 1
 CALIBRATION
 PMU 1
 TRIGGERING
 PMU 1
 RECORDING
C60 Breaker Protection System

PHASOR MEASUREMENT UNIT 1(2)
See page 5-128.
See page 5-132.
See page 5-133.
See page 5-141.