GE C60 Instruction Manual page 510

Breaker protection system ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 10 of 66)
ADDR
REGISTER NAME
Source Demand (Read Only) (4 modules)
1E00
Source 1 Demand Ia
1E02
Source 1 Demand Ib
1E04
Source 1 Demand Ic
1E06
Source 1 Demand Watt
B
1E08
Source 1 Demand Var
1E0A
Source 1 Demand Va
1E0C
Reserved (4 items)
1E10
...Repeated for Source 2
1E20
...Repeated for Source 3
1E30
...Repeated for Source 4
Source Demand Peaks (Read Only Non-Volatile) (4 modules)
1E80
Source 1 Demand Ia Maximum
1E82
Source 1 Demand Ia Maximum Date
1E84
Source 1 Demand Ib Maximum
1E86
Source 1 Demand Ib Maximum Date
1E88
Source 1 Demand Ic Maximum
1E8A
Source 1 Demand Ic Maximum Date
1E8C
Source 1 Demand Watt Maximum
1E8E
Source 1 Demand Watt Maximum Date
1E90
Source 1 Demand Var
1E92
Source 1 Demand Var Maximum Date
1E94
Source 1 Demand Va Maximum
1E96
Source 1 Demand Va Maximum Date
1E98
Reserved (8 items)
1EA0
...Repeated for Source 2
1EC0
...Repeated for Source 3
1EE0
...Repeated for Source 4
Breaker Flashover (Read/Write Setting) (2 modules)
2196
Breaker Flashover 1 Function
2197
Breaker Flashover 1 Side 1 Source
2198
Breaker Flashover 1 Side 2 Source
2199
Breaker Flashover 1 Status Closed A
219B
Breaker Flashover 1 Status Closed B
219D
Breaker Flashover 1 Status Closed C
219F
Breaker Flashover 1 Voltage Pickup Level
21A0
Breaker Flashover 1 Voltage Difference Pickup Level
21A2
Breaker Flashover 1 Current Pickup Level
21A3
Breaker Flashover 1 Pickup Delay
21A4
Breaker Flashover 1 Supervision Phase A
21A6
Breaker Flashover 1 Supervision Phase B
21A8
Breaker Flashover 1 Supervision Phase C
21AA
Breaker Flashover 1 Block
21AC
Breaker Flashover 1 Events
21AD
Breaker Flashover 1 Target
21AE
Reserved (4 items)
21B2
...Repeated for Breaker Flashover 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21E0
Breaker 1 Arcing Current Phase A
21E2
Breaker 1 Arcing Current Phase B
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21E4
Breaker 1 Arcing Current Phase C
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21E6
Breaker 1 Operating Time Phase A
B-18
RANGE
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
---
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
---
0 to 1
0 to 5
0 to 6
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1.5
0 to 100000
0 to 1.5
0 to 65.535
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 2
---
0 to 99999999
0 to 99999999
0 to 99999999
0 to 65535
C60 Breaker Protection System
APPENDIX B
UNITS
STEP
FORMAT
A
0.001
F060
A
0.001
F060
A
0.001
F060
W
0.001
F060
var
0.001
F060
VA
0.001
F060
---
---
F001
A
0.001
F060
---
1
F050
A
0.001
F060
---
1
F050
A
0.001
F060
---
1
F050
W
0.001
F060
---
1
F050
var
0.001
F060
---
1
F050
VA
0.001
F060
---
1
F050
---
---
F001
---
1
F102
---
1
F167
---
1
F211
---
1
F300
---
1
F300
---
1
F300
pu
0.001
F001
V
1
F060
pu
0.001
F001
s
0.001
F001
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F109
---
---
F001
2
kA
-cyc
1
F060
2
kA
-cyc
1
F060
2
kA
-cyc
1
F060
ms
1
F001
DEFAULT
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (Disabled)
0 (SRC 1)
0 (None)
0
0
0
850
1000
600
100
0
0
0
0
0 (Disabled)
0 (Self-Reset)
0
0
0
0
0
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents