GE C60 Instruction Manual page 332

Breaker protection system ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
c) PHASE OVERVOLTAGE (ANSI 59P, IEC PTOV)

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE
 OVERVOLTAGE1
There are three phase overvoltage elements available. A phase overvoltage element is used as an instantaneous element
5
with no intentional time delay or as a definite time element. The input voltage is the phase-to-phase voltage, either mea-
sured directly from delta-connected VTs or as calculated from phase-to-ground (wye) connected VTs. The specific voltages
to be used for each phase are shown below.
If the source VT is wye-connected, then the phase overvoltage pickup condition is
and V
.
CA
NOTE
5-196
SETTING GROUP 1(6)
PHASE OV1
FUNCTION: Disabled
PHASE OV1 SIGNAL
MESSAGE
SOURCE: SRC 1
PHASE OV1
MESSAGE
PICKUP: 1.000 pu
PHASE OV1 PICKUP
MESSAGE
DELAY:
PHASE OV1 RESET
MESSAGE
DELAY:
PHASE OV1 BLOCK:
MESSAGE
Off
PHASE OV1
MESSAGE
TARGET: Self-reset
PHASE OV1
MESSAGE
EVENTS: Disabled
Figure 5–81: PHASE OVERVOLTAGE SCHEME LOGIC
C60 Breaker Protection System

VOLTAGE ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: FlexLogic Operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS

PHASE OVERVOLTAGE1(3)
>
×
V
3
Pickup
for V
, V
AB
GE Multilin
,
BC