GE C60 Instruction Manual page 459

Breaker protection system ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

7 COMMANDS AND TARGETS
MAINTENANCE ALERT:
4L Discrepancy
Latched target message: No.
Description of problem: A discrepancy has been detected between the actual and desired state of a latching contact
output of an installed type "4L" module.
How often the test is performed: Upon initiation of a contact output state change.
What to do: Verify the state of the output contact and contact the factory if the problem persists.
MAINTENANCE ALERT:
GGIO Ind xxx oscill
Latched target message: No.
Description of problem: A data item in a configurable GOOSE data set is oscillating.
How often the test is performed: Upon scanning of each configurable GOOSE data set.
What to do: The "xxx" text denotes the data item that has been detected as oscillating. Evaluate all logic pertaining to
this item.
DIRECT I/O FAILURE:
COMM Path Incomplete
Latched target message: No.
Description of problem: A direct device is configured but not connected.
How often the test is performed: Every second.
What to do: Check direct input and output configuration and wiring.
REMOTE DEVICE FAIL:
COMM Path Incomplete
Latched target message: No.
Description of problem: One or more GOOSE devices are not responding.
How often the test is performed: Event driven. The test is performed when a device programmed to receive GOOSE
messages stops receiving. This can be from 1 to 60 seconds, depending on GOOSE packets.
What to do: Check GOOSE setup.
AGGREGATOR ERROR:
Latched target message: No.
Description of problem: The second line of this self-test error indicates the problem with the PMU Aggregator.
How often the test is performed: Each time a PMU's related settings is changed.
What to do: Correct the problem indicated in the second line or contact the factory.
TEMP MONITOR:
OVER TEMPERATURE
Latched target message: Yes.
Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C).
How often the test is performed: Every hour.
GE Multilin