GE C60 Instruction Manual page 164

Breaker protection system ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
RS485 COM2 RESPONSE MIN TIME
ing data from a host. This feature allows operation with hosts that hold the RS485 transmitter active for some time after
each transmission.
c) ETHERNET NETWORK TOPOLOGY
The C60 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP
address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND oper-
ation performed between their respective IP address and mask produces a different result. Communication becomes
unpredictable when more than one port is configured to the same subnet.
Example 1
IP1/Mask1: 10.1.1.2/255.255.255.0 (where LAN 1 is 10.1.1.x/255.255.255.0)
IP2/Mask2: 10.2.1.2/255.255.255.0 (where LAN2 is 10.2.1.x/255.255.255.0)
IP3/Mask3: 10.3.1.2/255.255.255.0 (where LAN3 is 10.3.1.x/255.255.255.0)
Example 2
IP1/Mask1: 10.1.1.2/255.0.0.0 (where LAN1 is 10.x.x.x/255.0.0.0)
IP2/Mask2: 11.1.1.2/255.0.0.0 (where LAN2 is 11.x.x.x/255.0.0.0)
IP3/Mask3: 12.1.1.2/255.0.0.0 (where LAN3 is 12.x.x.x/255.0.0.0)
Example 3 — Incorrect
IP1/Mask1: 10.1.1.2/255.0.0.0
IP2/Mask2: 10.2.1.2/255.0.0.0
5
IP3/Mask3: 10.3.1.2/255.0.0.0
This example is incorrect because the mask of 255.0.0.0 used for the three IP addresses makes them belong to the same
network of 10.x.x.x.
Single LAN, No Redundancy
The topology shown in the following figure allows communications to SCADA, local configuration/monitoring through
EnerVista, and access to the public network shared on the same LAN. No redundancy is provided.
5-28
: This setting specifies the minimum time before the rear RS485 port transmits after receiv-
Figure 5–4: NETWORK CONFIGURATION FOR SINGLE LAN
Public Network
EnerVista Software
LAN1
P1
IP1/
MAC1
C60 Breaker Protection System
SCADA
ML3000
P2
P3
UR
859708A2.vsd