Resetting - GE C60 Instruction Manual

Breaker protection system ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

5.8 INPUTS AND OUTPUTS
Remote outputs (1 to 32) are FlexLogic operands inserted into GSSE/GOOSE messages that are transmitted to remote
devices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic oper-
and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted.
Table 5–33: IEC 61850 DNA ASSIGNMENTS
DNA
IEC 61850 DEFINITION
1
Test
2
ConfRev
b) USERST BIT PAIRS

PATH: SETTINGS
INPUTS/OUTPUTS
 REMOTE OUTPUTS
 UserSt- 1 BIT PAIR
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the
message must be programmed to carry the state of a specific FlexLogic operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
For more information on GSSE/GOOSE messaging, see the Remote Inputs/Outputs Overview in the Remote
Devices section.
NOTE
5

PATH: SETTINGS
INPUTS/OUTPUTS
 RESETTING
Some events can be programmed to latch the faceplate LED event indicators, target message, and/or graphical panel
annunciator windows. Once set, the latching mechanism holds all of the latched indicators or messages in the set state
after the initiating condition has cleared until a RESET command is received to return these latches (not including FlexLogic
latches) to the reset state where the initiating condition has cleared. The RESET command can be sent from the faceplate
Reset button, a remote device via a communications channel, or any selected operand.
The three sources of RESET commands each activates the
RESET command also creates its individual operand
to identify the source of the command. Each of these three operands generates an event in the event record when
AND)
activated. The setting shown above selects the operand that activates the
5-264
FLEXLOGIC OPERAND
IEC 61850 TEST MODE
IEC 61850 CONF REV

REMOTE OUTPUTS UserSt BIT PAIRS
UserSt- 1 OPERAND:
Off
UserSt- 1 EVENTS:
MESSAGE
Disabled


RESETTING

RESET OPERAND:
Off
C60 Breaker Protection System
REMOTE OUTPUTS UserSt- 1(32) BIT PAIR
Range: FlexLogic operand
Range: Disabled, Enabled
Range: FlexLogic operand
FlexLogic operand. Each individual source of a
RESET OP
,
RESET OP (PUSHBUTTON)
RESET OP (COMMS),
RESET OP (OPERAND)
5 SETTINGS
5.8.9 RESETTING
or
RESET OP (OPER-
operand.