2.4 SPECIFICATIONS
PHASE OVERVOLTAGE
Voltage:
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Operate time:
2
Timer accuracy:
NEUTRAL OVERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Reset delay:
Curve timing accuracy
at >1.1 x pickup:
Operate time:
AUXILIARY OVERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Reset delay:
Timer accuracy:
Operate time:
BREAKER FAILURE
Mode:
Current supervision:
Current supv. pickup:
Current supv. dropout:
Current supv. accuracy:
0.1 to 2.0 × CT rating: ±0.75% of reading or ±2% of rated
above 2 × CT rating:
BREAKER ARCING CURRENT
Principle:
Initiation:
Compensation for auxiliary relays: 0 to 65.535 s in steps of 0.001
Alarm threshold:
Fault duration accuracy: 0.25 of a power cycle
Availability:
2-20
Phasor only
0.000 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0.00 to 600.00 in steps of 0.01 s
<30 ms at 1.10 × pickup at 60 Hz
±3% of operate time or ±1/4 cycle
(whichever is greater)
0.000 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0.00 to 600.00 s in steps of 0.01 (definite
time) or user-defined curve
0.00 to 600.00 s in steps of 0.01
±3.5% of operate time or ±1 cycle
(whichever is greater) from pickup to
operate
<30 ms at 1.10 × pickup at 60 Hz
0.000 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0 to 600.00 s in steps of 0.01
0 to 600.00 s in steps of 0.01
±3% of operate time or ±1/4 cycle
(whichever is greater)
<30 ms at 1.10 × pickup at 60 Hz
1-pole, 3-pole
phase, neutral current
0.001 to 30.000 pu in steps of 0.001
97 to 98% of pickup
(whichever is greater)
±2.5% of reading
2
accumulates breaker duty (I
t) and mea-
sures fault duration
programmable per phase from any Flex-
Logic operand
2
0 to 50000 kA
-cycle in steps of 1
1 per CT bank with a minimum of 2
C60 Breaker Protection System
2 PRODUCT DESCRIPTION
BREAKER FLASHOVER
Operating quantity:
phase current, voltage and voltage differ-
ence
Pickup level voltage:
0 to 1.500 pu in steps of 0.001
Dropout level voltage:
97 to 98% of pickup
Pickup level current:
0 to 1.500 pu in steps of 0.001
Dropout level current:
97 to 98% of pickup
Level accuracy:
±0.5% or ±0.1% of rated, whichever is
greater
Pickup delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±42 ms, which-
ever is greater
<42 ms at 1.10 × pickup at 60 Hz
Operate time:
BREAKER RESTRIKE
Principle:
detection of high-frequency overcurrent
condition ¼ cycle after breaker opens
Availability:
one per CT/VT module (not including 8Z
modules)
Pickup level:
0.1 to 2.00 pu in steps of 0.01
Reset delay:
0.000 to 65.535 s in steps of 0.001
SYNCHROCHECK
Max voltage difference: 0 to 400000 V in steps of 1
Max angle difference:
0 to 100
Max freq. difference:
0.00 to 2.00 Hz in steps of 0.01
Hysteresis for max. freq. diff.: 0.00 to 0.10 Hz in steps of 0.01
Dead source function:
None, LV1 & DV2, DV1 & LV2, DV1 or
DV2, DV1 xor DV2, DV1 & DV2
(L = Live, D = Dead)
AUTORECLOSURE
Two breakers applications
Single- and three-pole tripping schemes
Up to 4 reclose attempts before lockout
Selectable reclosing mode and breaker sequence
OPEN POLE DETECTOR
Functionality:
Detects an open pole condition, monitor-
ing breaker auxiliary contacts, the cur-
rent in each phase and optional voltages
on the line
Current pickup level:
0.000 to 30.000 pu in steps of 0.001
Line capacitive reactances (X
, X
C1
steps of 0.1
Remote current pickup level: 0.000 to 30.000 pu in steps of 0.001
Current dropout level:
pickup + 3%, not less than 0.05 pu
THERMAL OVERLOAD PROTECTION
Thermal overload curves: IEC 255-8 curve
Base current:
0.20 to 3.00 pu in steps of 0.01
Overload (k) factor:
1.00 to 1.20 pu in steps of 0.05
Trip time constant:
0 to 1000 min. in steps of 1
Reset time constant:
0 to 1000 min. in steps of 1
Minimum reset time:
0 to 1000 min. in steps of 1
Timer accuracy (cold curve): ±100 ms or 2%, whichever is greater
Timer accuracy (hot curve): ±500 ms or 2%, whichever is greater
for I
< 0.9 × k × I
p
°
in steps of 1
): 300.0 to 9999.9 sec. Ω in
C0
and I / (k × I
) > 1.1
b
b