5.4 SYSTEM SETUP
PMU 1 POWER TRIGGER REACTIVE: This setting specifies the pickup threshold for the reactive power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
PMU 1 POWER TRIGGER APPARENT: This setting specifies the pickup threshold for the apparent power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
PMU 1 POWER TRIGGER PKP TIME: This setting can be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
PMU 1 POWER TRIGGER DPO TIME: This setting can be used to extend the trigger after the situation returned to
normal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the
triggering condition is asserted).
5
j) DF/DT TRIGGERING

PATH: SETTINGS
SYSTEM SETUP
 PMU 1 df/dt
 TRIGGER
5-138
Figure 5–51: POWER TRIGGER SCHEME LOGIC

PHASOR MEASUREMENT...
PMU 1 df/dt TRIGGER
FUNCTION: Disabled
PMU 1 df/dt TRIGGER
MESSAGE
RAISE: 0.25 Hz/s
PMU 1 df/dt TRIGGER
MESSAGE
FALL: 0.25 Hz/s
PMU 1 df/dt TRIGGER
MESSAGE
PKP TIME: 0.10 s
PMU 1 df/dt TRIGGER
MESSAGE
DPO TIME: 1.00 s
PMU 1 df/dt TRG BLK:
MESSAGE
Off
PMU 1 df/dt TRIGGER
MESSAGE
TARGET: Self-Reset
PMU 1 df/dt TRIGGER
MESSAGE
EVENTS: Disabled
C60 Breaker Protection System


PMU 1(2) TRIGGERING
Range: Enabled, Disabled
Range: 0.10 to 15.00 Hz/s in steps of 0.01
Range: 0.10 to 15.00 Hz/s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Enabled, Disabled
5 SETTINGS