3.2 Configure the module parameters

In this section, we will describe how to configure the communication
parameters of the I-7530A-MR module with the UART2CAN Utility.
3.2.1
Connect to the I-7530A-MR module with UART2CAN Utility
1. Set the Init/Normal switch to the "Normal" position, which is found
on the back of the I-7530A-MR module.
2. Supply the proper electric power (the 10~30 DC volts) to the I-
7530A-MR module.
3. Set the Init/Normal switch to the "Init" (Initial) position at least three
seconds.
4. The PWR LED of the I-7530A-MR module will turned on and the
other LEDs will flash approximately once per second. That means
the I-7530A-MR module is working in the configuration mode.
5. Run the UART2CAN Utility software after connecting the PC COM
port and the I-7530A-MR RS-232 port by the cable CA-0910.
6. Select the necessary PC COM port to connect with the I-7530A-MR,
as shown in the following figure. Then click the "Connect" button.
Figure 3-7: The PC's COM port configuration form.
Note: When the I-7530A-MR is working in the configuration mode, it can
only be communicated by using 115200 baud rate.
I-7530A-MR Modbus RTU to CAN Converter User's Manual (Version 1.07, 06/2016) ------------- 25