AsciiToHex(FF)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Table 4-4: CAN and RS-232/485/422 FIFO overflow flag list
AsciiToHex(O)
Bit 3
Bit 2
Bit 1
Bit 0
 Example:
Command: S<CR>
Receive: !50000000<CR>
Obtain some current information on the I-7530A-MR module. The
response will show the following results: CAN baud rate=250K, CAN
status register= normal, CAN transmit error counter=0, CAN receive
error counter=0 and CAN & RS232/485/422 FIFO= normal.
4.6 P0BBDSPCR[CHK]<CR>
Description: Change the RS-232/485/422 configuration on the I-7530A-MR
module and then reboot the I-7530A-MR module.
 Syntax: P0BBDSPCR[CHK]<CR>
I-7530A-MR Modbus RTU to CAN Converter User's Manual (Version 1.07, 06/2016) ------------- 55
4
125K baud rate of CAN
5
250K baud rate of CAN
6
500K baud rate of CAN
7
800K baud rate of CAN
8
1000K baud rate of CAN
F
User-defined baud rate of CAN
Table 4-3: CAN status register list
Bus Status (0: Bus-On, 1: Bus-Off)
Error Status (0: OK, 1: Error)
Transmit Status (0: idle, 1: transmit )
Receive Status (0:idle, 1: Receive)
Transmit Complete Status (0: incomplete, 1: complete)
Receive Complete Status (0: incomplete, 1: complete)
Data Overrun Status (0: absent, 1: overrun)
Receive Buffer Status (0: empty, 1: full)
Reserved
Reserved
RS-232/485/422 FIFO Overflow
CAN FIFO Overflow
Description
Description