Command List (Only For Normal Mode) - ICP DAS USA I-7530A-MR User Manual

Modbus rtu to can converter
Hide thumbs Also See for I-7530A-MR:
Table of Contents

Advertisement

4. Command list (Only for normal mode)

In order to simplify the application, we provide 9 command strings to
send/receive commands through the I-7530A-MR. It can cover most of
the applications. The general formats of the commands for the I-7530A-
MR are given below:
Command Format: <Command>[CHK]<CR>
<Command> : RS-232/485/422 commands of the I-7530A-MR
[CHK]
: 2-character checksum value. It is effective only if the
<CR>
: All RS-232/485/422 commands of the I-7530A-MR must
The 9 command formats are given in the following table. More
detailed information related to the each command will be described in the
following sub sections.
Command
tIIILDD...[CHK]<CR>
TIIIL[CHK]<CR>
eIIIIIIIILDD...[CHK]<CR> Send or receive an extended data frame.
EIIIIIIIIL[CHK]<CR>
S[CHK]<CR>
P0BBDSPCE[CHK]<CR> *Change the RS-232/485/422 configuration
P1B [CHK]<CR>
P2BBBBB[CHK]<CR>
RA[CHK]<CR>
* NOTE:
This command will write parameters into EEPROM and
EEPROM is limited to 10,000,000 erase/write cycles.
I-7530A-MR Modbus RTU to CAN Converter User's Manual (Version 1.07, 06/2016) ------------- 50
checksum mechanism is set to enable by using
UART2CAN Utility.
to page 51
be ended with the character "<CR>" (The ASCII value is
13).
Table 4-1: Command list table
Send or receive a standard data frame.
Send or receive a standard remote frame.
Send or receive an extended remote frame.
Read the status value of the I-7530A-MR
*Change the CAN Baud rate configuration
*Change the user-defined CAN baud rate
configuration
Reboot the I-7530A-MR module.
For checksum algorithm, please refer
Description