3.1

How to configure the module parameters

1. Set the Init/Normal switch to the Init position, which is located at the
back of the I-7530 module.
2. Connect the power source (the 10~30 DC volts) into the I-7530 module.
3. The I-7530 module's ON LED will flash approximately once per second.
That means the I-7530 module is working in the configuration mode.
4. Run the I-7530's Utility software after connect the PC COM port and the
I-7530 COM port by a RS-232 cable.
5. Click the "Connect" icon on the I-7530 Utility tool bar. The setting frame
will be popped up. Select which PC COM port will be used to connect to
the I-7530 COM port, as shown in the following figure. Then click the
"OK" button.
I-7530 RS-232/CAN Converter User's Manual (Version 2.0, Sep/2007) ------------- 14