For example, if users want to pass the CAN port with CAN ID 0x07F
in the CAN 2.0B specification.
Step1: Select "29-bit ID" item in the "CAN Single CAN ID" field.
Step2: Fill the value "7F" in the edit box.
Step3: Click "Add" button in the "CAN Single CAN ID" field.
Another example, if users want to pass the CAN port with CAN ID
from 0x04 to 0x15 in the CAN 2.0A specification.
Step1: Select "11-bit ID" item in the "CAN Group CAN ID" field.
Step2: Fill the value "4" in the "Start" field and the value "15" in the "End"
field.
Step3: Click "Add" button in the "CAN Group CAN ID" field.
After completing these two examples, users will see the follow figure.
The "No." field means that the sequential number of the CAN filter setting.
The "CAN Port" field means that the filter setting is belong to which CAN
port. In the I-7530A-MR module, users don't need to care about this field.
The "Accepted IDs" field means that which CAN ID can be passed.
There are four small icon pictures which represent some information.
This icon means that this CAN filter is 11-bit and single CAN ID.
This icon means that this CAN filter is 11-bit and group CAN ID.
This icon means that this CAN filter is 29-bit and single CAN ID.
This icon means that this CAN filter is 29-bit and group CAN ID.
Step 4: When completing the CAN filter configuration, click the "Save to
File" button to save it for backup. It will save the filter data with "*.FLT"
I-7530A-MR Modbus RTU to CAN Converter User's Manual (Version 1.07, 06/2016) ------------- 34