Init / Normal Dip-Switch - ICP DAS USA I-7530A-MR User Manual

Modbus rtu to can converter
Hide thumbs Also See for I-7530A-MR:
Table of Contents

Advertisement

Enable (default)
Disable
Figure 2-10: Terminal resistor JP3 Jumper Position

2.5 Init / Normal Dip-switch

On the back of the I-7530A-MR module, there is a DIP-switch used to
configure the "firmware operation mode", "firmware update mode" or
"module configuration mode". The following steps show how to use it.
2.5.1
Firmware Update Mode
Please set the DIP-switch to the "Init" (Initial) position as Figure 2-12,
and then the I-7530A-MR will work in the "Firmware Update Mode" after
resetting the power of the module. In the firmware update mode, users
can update the firmware of the I-7530A-MR module from computer's RS-
232 port via CA-0910 cable, as Figure 2-12~2-14.
Figure 2-12: Init Position of DIP-Switch
I-7530A-MR Modbus RTU to CAN Converter User's Manual (Version 1.07, 06/2016) ------------- 15