P1B [Chk]<Cr - ICP DAS USA I-7530A-MR User Manual

Modbus rtu to can converter
Hide thumbs Also See for I-7530A-MR:
Table of Contents

Advertisement

4.7 P1B [CHK]<CR>
Description: Change the CAN Baud rate configuration of the I-7530A-MR
module and then reboot the I-7530A-MR module.
 Syntax: P1B[CHK]<CR>
P1
B
9,A,B,C,D,E Reserved
 Response: A valid command will write the CAN configuration baud rate
into the EEPROM and then reboot the I-7530A-MR module.
Note: It is necessary to enable the "Error Response" function while using
the UART2CAN Utility in order to receive Syntax and/or communication
error information.
 Example:
Command: P14<CR>
Set the CAN baud rate=125 kbps into the I-7530A-MR module and
then reboot the I-7530A-MR module.
I-7530A-MR Modbus RTU to CAN Converter User's Manual (Version 1.07, 06/2016) ------------- 58
Command character
CAN Baud rate
Table 4-7: CAN baud rate list
B
0
10 kbps baud rate of CAN
1
20 kbps baud rate of CAN
2
50 kbps baud rate of CAN
3
100 kbps baud rate of CAN
4
125 kbps baud rate of CAN
5
250 kbps baud rate of CAN
6
500 kbps baud rate of CAN
7
800 kbps baud rate of CAN
8
1000 kbps baud rate of CAN
F
User-defined baud rate of CAN
Invalid command: ?<Error Code><CR>
Description

Advertisement

Table of Contents
loading

Table of Contents