9.3.7
7yyy / 9999 - Erasing data from the
SMARTCARD
Data can be erased from the SMARTCARD one data block at a time or
with data blocks 1 to 499 in selected together.
Setting 7yyy in Pr xx.00 will erase SMARTCARD data block yyy
Setting 9999 in Pr xx.00 will erase SMARTCARD data blocks 1 to
499
9.3.8
9666 / 9555 - Set / clear SMARTCARD warning
suppression flag
1. If the Solutions Module(s) installed to the source and destination
drive are different, or are in different slots, the drive will produce a
'C.Optn' trip.
2. If the data is being transferred to a drive of a different voltage or
current rating a 'C.rtg' trip will occur.
It is possible to suppress these trips by setting the warning suppression
flag. If this flag is set the drive will not trip if the Solutions Module(s) or
drive ratings are different between the source and the destination drives.
The Solutions Module or rating dependent parameters will not be
transferred.
Setting 9666 in Pr xx.00 will set the warning suppression flag
Setting 9555 in Pr xx.00 will clear the warning suppression flag
9.3.9
9888 / 9777 - Set / clear the SMARTCARD read
only flag
The SMARTCARD may be protected from writing or erasing by setting
the read only flag. If an attempt is made to write or erase a data block
when the read only flag is set, a 'C.rdo' trip is initiated.
When the read only flag is set only codes 6yyy or 9777 are effective.
Setting 9888 in Pr xx.00 will set the read only flag
Setting 9777 in Pr xx.00 will clear the read only flag
9.4

Data block header information

Each data block stored on a SMARTCARD has header information
detailing the following:
A number which identifies the data block (Pr 11.37)
Type of data stored in the data block (Pr 11.38)
Drive mode if the data is parameter data (Pr 11.38)
Version number (Pr 11.39)
Checksum (Pr 11.40)
Read-only flag
Warning suppression flag
The header information for each data block that has been used can be
viewed in Pr 11.38 to Pr 11.40 by increasing or decreasing the data block
number set in Pr 11.37.
If Pr 11.37 is set to 1000: the checksum parameter (Pr 11.40) shows the
number of bytes left on the card in 16 byte pages.
If Pr 11.37 is set to 1001: the checksum parameter (Pr 11.40) shows the
total capacity of the card in 16 byte pages. Therefore, for a 4kB card this
parameter would show 254.
If Pr 11.37 is set to 1002: the checksum parameter (Pr 11.40) shows the
state of the read-only (bit 0) and warning suppression flags (bit 1).
If there is no data on the card: Pr 11.37 can only have values of 0 or
1000 to 1002.
9.5

SMARTCARD parameters

11.36
SMARTCARD parameter data previously loaded
RO
Uni
NC
0 to 999
This parameter shows the number of the data block last parameter or
difference from default data block transferred from a SMARTCARD to
the drive.
Mentor MP User Guide
Issue: 3
Electrical
Getting
Basic
Running the
installation
started
parameters
PT
US
0
www.controltechniques.com
SMARTCARD
Optimization
motor
operation
11.37
SMARTCARD data number
RW
Uni
NC
0 to 1002
This parameter shows the data blocks that are stored on a
SMARTCARD with header information, including a number to identify
the data block.
11.38
SMARTCARD data type/mode
RO
Txt
NC
0 to 18
This parameter gives the type/mode of the data block selected with
Pr 11.37 as shown in the following table.
Table 9-4 Pr 11.38 types and modes
Pr 11.38
String
0
FrEE
1
3C.SE
2
3OpEn.LP
3
3CL.VECt
4
3SErVO
5
3REGEn
6
3DC
7
3Un
8
3Un
9
4C.SE
10
4OpEn.LP
11
4CL.VECt
12
4SErVO
13
4REGEn
14
4DC
15 & 16
4Un
17
LAddEr
18
Option
11.39
SMARTCARD data version
RW
Uni
NC
0 to 9999
This parameter gives the version number of the data block.
11.40
SMARTCARD data checksum
RO
Uni
NC
0 to 65335
This parameter gives the checksum of the data block, space left on the
card, the total space on the card or the card flags. Refer to Pr 11.37 for
information.
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
PT
Type/Mode
Value when Pr 11.37 = 0
Commander SE mode parameter file
(not used)
Open-loop mode parameter file
Closed-loop vector mode parameter file
Servo mode parameter file
Regen mode parameter file
DC mode parameter file
Unused
Unused
Commander SE mode difference from default
file (not used)
Open-loop mode difference from default file
Closed-loop vector mode difference from
default file
Servo mode difference from default file
Regen mode difference from default file
DC Mode difference from default file
Unused
Onboard Application Lite user program file
A file containing user defined data (the file is
normally created by an SM-Applications
Solutions Module)
PT
UL
information
0
0
0
83