Table 12-12 Auxiliary Wiring For Size 1 Drives; Table 12-13 Typical Cable Sizes For Size 2 Drives; Table 12-14 Auxilliary Wiring For Size 2 Drives - Emerson MP25A4 User Manual

Mentor mp series high performance dc drive 25a to 7400a, 480v to 690v two or four quadrant operation
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
information
Installation

Table 12-12 Auxiliary wiring for size 1 drives

Maximum
Continuous
input
Frame
current
size
A
1
13
Notes for IEC 60364:
IEC 60364-5-52 use installation method B2, Table A.52-4 for three loaded conductors, PVC insulation 30°C and apply derating factor for 40°C from
Table A.52-14 (0.87 for PVC).
Notes for UL508C:
Either 60°C or 75°C cable can be used. Ampacities as per table 40.3 as described in the UL508C standard.

Table 12-13 Typical cable sizes for size 2 drives

Model
MP350A4(R)
MP350A5(R)
MP420A4(R)
MP470A5(R)
MP550A4(R)
MP700A4(R)
MP700A5(R)
MP825A4(R)
MP825A5(R)
MP900A4(R)
MP1200A4(R)
MP1200A5(R)
MP1850A4(R)
MP1850A5(R)
* Values are beyond the mechanical design of the drive. At this power level it may be prudent to consider bus-bars.
Notes for IEC 60364:
NOTE
1. IEC 60364-5-52 Table A 52-12 F method column 5 = Single core cable in free air.
2. IEC 60364-5-52 table A52-14 correction factor for ambient air temperature others than 30°C.
3. IEC 60364-5-52 table A52-17 item 4 correction factor for groups of more than one circuit or more than one multi-core cable placed on a single
layer on a perforated tray.
NOTE
Notes for US National Electrical Code:
1. Table 310.17 allowable ampacities of single-insulated conducted rated 0 through 2000V in free air, based on ambient air temperature of 30°C
(87°F).
2. Derating factor of 0.88 is applied for 40°C to the 75°C cable column. Table 310.17 is based on 30°C (86°F) ambient air temperature.
3. NEC 2005 edition Table 310.15(B)(2)(a) shows the adjustment factors for more than three current-carrying conductors in a race way or cable, for
4-6 current-carrying conductors 0.80 derating factor is applied.

Table 12-14 Auxilliary wiring for size 2 drives

Maximum
Continuous
input
Frame size
current
A
2
23
Notes for IEC 60364:
IEC 60364-5-52 use installation method B2, Table A.52-4 for three loaded conductors, PVC insulation 30°C and apply derating factor for 40°C from
Table A.52-14 (0.87 for PVC).
Notes for UL508C: Either 60°C or 75°C cable can be used. Ampacities as per table 40.3 as described in the UL508C standard.
152
Electrical
Getting
Basic
installation
started
parameters
IEC 60364-5-52 Table A52-4 Column B2
output
Column B2 derated by 0,87 of PVC at 40
current
E1, E3 size
²
A
mm
8
2.5
Maximum
input
current
A
MP350A6(R)
313
375
MP470A6(R)
420
492
MP700A6(R)
626
MP825A6(R)
738
805
MP1200A6(R)
1073
MP1850A6(R)
1654
IEC 60364-5-52 Table A52-4 Column B2
output
Column B2 derated by 0,87 of PVC at 40
current
E1, E3 size
²
A
mm
20
6
www.controltechniques.com
Running the
SMARTCARD
Optimization
motor
operation
F+, F- , L11 & L12 size
²
mm
1.5
IEC 60364-5-52 Table A52-
12 Column 5 derated by
0.91 for 40°C XLPE cables
(IEC 60364-5-52 table A52-
Continuous
14) and 0.77 for cables
output current
bunching (IEC 60364-5-52
table A52-17 item 4)
90°C cables at 40°C
Input size
A
mm²
350
120
420
150
470
185
550
300
700
2 x 150
825
2 x 185
900
2 x 185
1200
2 x 300
1850
4 x 240
F+, F- , L11 & L12 size
²
mm
4
Onboard
Advanced
Technical
PLC
parameters
data
UL 508C
E1, E3 size
F+, F- , L11 & L12 size
²
mm
14 AWG
US National
Electrical Code
75°C cable at 40°C ambient
ambient
Output size
Input cables
mm²
Kcmil
150
350
185
400
240
500
2 x 185
2 x 300
2 x 150
2 x 500
2 x 240
2 x 600
2 x 240
3 x 350
3 x 240
3 x 600
4 x 300
*
UL 508C
E1, E3 size
F+, F- , L11 & L12 size
²
mm
10 AWG
Mentor MP User Guide
UL
Diagnostics
information
²
mm
14 AWG
Output cables
Kcmil
400
500
600
2 x 350
2 x 600
3 x 350
3 x 400
4 x 400
*
²
mm
10 AWG
Issue: 3