Table 12-44 Emission Compliance - Emerson MP25A4 User Manual

Mentor mp series high performance dc drive 25a to 7400a, 480v to 690v two or four quadrant operation
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
information
Installation
Emission
The requirements of the following standards are met for motor cable
lengths up to 100m.

Table 12-44 Emission compliance

Model
Field: Standard
None
Armature: Standard
MP25A4(R)
MP45A4(R)
MP75A4(R)
MP105A4(R)
MP155A4(R)
MP210A4(R)
MP350A4(R)
C4
MP420A4(R)
MP550A4(R)
MP700A4(R)
MP825A4(R)
MP900A4(R)
MP1200A4(R)
MP1850A4(R)
Key (shown in decreasing order of permitted emission level):
C4
EN 61800-3 second environment, restricted distribution
(Additional measures may be required to prevent interference)
C3
EN 61800-3 second environment, unrestricted distribution
C2
Industrial generic standard EN 50081-2 (EN 61000-6-4)
EN 61800-3 first environment restricted distribution (The
following caution is required by EN 61800-3)
This is a product of the restricted distribution class according
to IEC 61800-3. In a residential environment this product may
cause radio interference in which case the user may be
required to take adequate measures.
CAUTION
C1
Residential generic standard EN 50081-1 (EN 61000-6-3)
EN 61800-3 first environment unrestricted distribution
EN 61800-3 defines the following:
The first environment is one that includes residential premises. It
also includes establishments directly connected without intermediate
transformers to a low-voltage power supply network which supplies
buildings used for residential purposes.
The second environment is one that includes all establishments
other than those directly connected to a low-voltage power supply
network which supplies buildings used for residential purposes.
Restricted distribution is defined as a mode of sales distribution in
which the manufacturer restricts the supply of equipment to
suppliers, customers or users who separately or jointly have
technical competence in the EMC requirements of the application of
drives.
Mentor MP User Guide
Issue: 3
Electrical
Getting
Basic
Running the
installation
started
parameters
Filter
Field: Standard
Armature:High
performance
C3
C2
www.controltechniques.com
SMARTCARD
Optimization
motor
operation
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
UL
information
165