Cable And Fuse Size Ratings; Table 4-6 Typical Cable Sizes For Size 1 Drives - Emerson MP25A4 User Manual

Mentor mp series high performance dc drive 25a to 7400a, 480v to 690v two or four quadrant operation
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
information
Installation
It can be used as a back-up power supply to keep the control circuits
of the drive powered up when the line power supply is removed. This
allows any fieldbus modules, application modules, encoders or serial
communications to continue to operate.
It can be used to commission the drive when the line power supply is
not available, as the display operates correctly. However, the drive
will be in the UV trip state unless the line power supply is enabled,
therefore diagnostics may not be possible. (Power down save
parameters are not saved when using the 24V back-up power
supply input.)
The working voltage range of the 24V power supply is as follows:
Maximum continuous operating voltage:
Minimum continuous operating voltage:
Nominal operating voltage:
Minimum start up voltage:
Maximum power supply requirement at 24V:
Recommended fuse:
Minimum and maximum voltage values include ripple and noise. Ripple
and noise values must not exceed 5%.
4.6

Cable and fuse size ratings

The selection of the correct fuse is essential to ensure the
safety of the installation
WARNING
Maximum continuous input currents are given in section 2.1 Ratings on
page 6 to aid the selection of fuses and cabling. The maximum input
current is dependent on the ripple content of the output current. A value
of 100% ripple has been assumed for the given ratings.
The cable sizing selected when installing a Mentor MP must comply with
the local wiring regulations. The information provided in this section is
provided for guidance purposes only.
The power terminals on Mentor MP frame size 1 drives have been
designed to accommodate a maximum cable size of 150mm
with a temperature of 90°C (194°F).
The power terminals on Mentor MP frame size 2A drives have been
designed to accommodate a maximum cable size of 2 x 150mm
350kcmil) with a temperature of 75°C (167°F).
The power terminals on Mentor MP frame size 2B drives have been
designed to accommodate 2 x 240mm
(194°F). The use of cables sized using the US national electrical code as
shown in Table 4-8 requires the use of a terminal adaptor.
The power terminals on Mentor MP frame size 2C and 2D drives have
been designed for use with busbars. The drive can be used with cables
as shown in Table 4-8 with the use of a terminal adaptor.
The actual cable size depends on a number of factors including:
Actual maximum continuous current
Ambient temperature
Cable support, method and grouping
Cable voltage drop
In applications where the motor used is of a reduced rating, the cable
sizing selected can be appropriate for that motor. To protect the motor
and the output cabling the drive must be programmed with the correct
motor rated current.
NOTE
When using reduced cable sizes, the branch circuit protection fuse rating
needs to be reduced in line with the cable size selected.
The following table shows typical cable sizes based on USA and
International standards, assuming 3 conductors per raceway/conduit, an
ambient temperature of 40°C (104°F) and applications with high output
current ripple content.
38
Electrical
Getting
Basic
installation
started
parameters
30.0V
19.2V
24.0V
21.6V
60W
3 A, 50Vdc
2
(350kcmil)
2
with a temperature of 90°C
www.controltechniques.com
Running the
SMARTCARD
Optimization
motor
operation

Table 4-6 Typical cable sizes for size 1 drives

Model
MP25A4(R)
MP25A5(R)
MP45A4(R)
MP45A5(R)
MP75A4(R)
MP75A5(R)
MP105A4(R) MP105A5(R)
MP155A4(R) MP155A5(R)
MP210A4(R) MP210A5(R)
NOTE
1. The maximum cable size is defined by the power terminal housing
using 90°C (194°F) rated cables as per Table A.52-5 of the standard.
2. Assumes the use of 75°C rated cables, as per Table 310.16 of the
National Electrical Code.
The use of higher temperature rated cable would allow a reduction on
the minimum recommended cable size for Mentor MP shown above. For
high temperature cable sizing, please refer to the data supplied by the
manufacturer of the high temperature cable.
2
(2 x
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
[1]
IEC 60364-5-52
Input
Output
2
2
8 AWG
2.5mm
4mm
2
2
4 AWG
10mm
10mm
2
2
1 AWG
16mm
25mm
2
2
1/0 AWG 1/0 AWG
25mm
35mm
2
2
3/0 AWG 4/0 AWG
50mm
70mm
2
2
300kcmil
95mm
95mm
Mentor MP User Guide
UL
information
[2]
UL508C/NEC
Input
Output
8 AWG
4 AWG
1/0 AWG
350kcmil
Issue: 3