Table 4-24 Fan supply specification

Fan configuration
230V
115V
Cabling should be 300V rated. Rated for at least 3A continuous in line
with local wiring regulations. Cabling should be protected 3A non time
delay fuses i.e. gG, Class CC or Class J and rated for at least 300V, in
accordance with local wiring regulations.
4.13

Control connections

Refer to Figure 4-20 to understand the connection of the different power
connections.
4.13.1
General

Table 4-25 The control connections consist of:

Function
Qty
Destination, offset, invert,
Differential analog input
1
scaling
Single ended analog
Mode, offset, scaling, invert,
2
input
destination
Analog output
2
Source, mode, scaling,
Digital input
3
Destination, invert, logic select
Input / output mode select,
Digital input / output
3
destination / source, invert,
logic select
Relay
2
Source, invert
Drive enable
1
Logic select
+10V User output
1
+24V User output
1
0V common
6
+24V External input
1
Key:
Destination
Indicates the parameter which is being controlled by the
parameter:
terminal / function
Source
Indicates the parameter being output by the terminal
parameter:
Mode
Analog - indicates the mode of operation of the terminal,
parameter:
i.e. voltage 0-10V, current 4-20mA etc.
Digital - indicates the mode of operation of the terminal,
i.e. positive / negative logic, open collector.
All analog terminal functions can be programmed in menu 7.
All digital terminal functions (including the relays) can be programmed in
menu 8.
The setting of Pr 6.04 can cause the function of digital inputs T25 to T27
to change. For more information, refer to section 11.22.5 Start / stop
logic modes on page 143.
If the control circuits are to be connected to other circuits
classified as Safety Extra Low Voltage (SELV) (e.g. to a
personal computer), an additional isolating barrier must be
included in order to maintain the SELV classification.
WARNING
If any of the digital inputs (including the drive enable input)
are connected in parallel with an inductive load (i.e.
contactor or motor brake) then suitable suppression (i.e.
diode or varistor) should be used on the coil of the load. If no
CAUTION
suppression is used then over voltage spikes can cause
damage to the digital inputs on the drive.
50
Electrical
Getting
Basic
installation
started
parameters
Supply specification
230V ±10%
115V ±10%
Control parameters available
27, 28, 29
24, 25, 26
51, 52, 53
61, 62, 63
1, 3, 11, 21,
www.controltechniques.com
Running the
SMARTCARD
Optimization
motor
operation
The control circuits are isolated from the power circuits in the
drive by basic insulation (single insulation) only. The installer
must ensure that the external control circuits are insulated
from human contact by at least one layer of insulation
(supplementary insulation) rated for use at the AC supply
WARNING
voltage.
Status relay contacts are over-voltage category II.
WARNING
A fuse or other over-current protection should be installed to
the relay circuit.
Terminal
WARNING
number

Table 4-26 Control connection recommended cable sizes

5,6
Terminal
7,8
Machine armature
9,10
Auxiliary
Control I/O
Encoder
Tachogenerator
Status relays
31
4
22
23, 30
2
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
Minimum cable size
Maximum cable size
5mm
2
0.5mm
20 AWG
1.31mm
2.5mm
Mentor MP User Guide
UL
information
2
10 AWG
2
16 AWG
2
12 AWG
Issue: 3