4.3.4
Main AC supply (L1, L2, L3)

Table 4-1 Three phase AC supply

Specification
Maximum nominal supply
Tolerance
Minimum nominal supply
Tolerance
4.4

Line reactors

The Mentor MP, in common with all naturally commutated thyristor
drives, causes voltage notches at the input supply terminals. In order to
avoid disturbance to other equipment using the same supply, the
addition of external line inductance is strongly recommended in order to
restrict the depth of the notches imposed on the shared supply. This is
generally not necessary where a dedicated transformer is used to supply
the drive.
The following recommendations for added line inductance, have been
calculated based on the power drive systems standard: EN 61800-
3:2004 "Adjustable speed electrical power drive systems – Part 3: EMC
requirements and specific test methods".
NOTE
The current ratings specified in Table 4-2 are for typical motor currents
where the motor current ripple is no more than 50% of drive rating.
Table 4-2 Minimum required line inductance for a typical
application (50% ripple content)
Drive
System voltage
rated
400V
480V
575V
current
μH
μH
A
25
220
260
320
45
220
260
320
75
220
260
320
105
220
260
320
155
160
190
230
210
120
140
170
350
71
85
110
420
59
71
470
550
45
54
700
36
43
825
900
28
33
1200
21
25
1850
18
23
NOTE
1. The above assumes the supply has 1.5% impedance.
2. Assumes a minimum supply rating of 5kA and a maximum rating of
60kA.
Mentor MP User Guide
Issue: 3
Electrical
Getting
Basic
installation
started
parameters
Product voltage variant
480V
575V
480V
575V
+10%
24V
500V
-20%
-10%
Typical
Maximum
current
690V
rating
μH
μH
A
21
38
63
88
130
176
120
293
351
80
91
393
460
53
61
586
45
52
690
753
31
36
1004
29
32
1548
www.controltechniques.com
Running the
SMARTCARD
Optimization
motor
operation
4.4.1
Auxiliary AC supply and connections

Table 4-3 Terminal functions

Terminals
690V
E1, E3
Supply for control electronics and field controller.
690V
Field on / off. When L11 and L12 are open the supply is
L11, L12
disconnected to the field regulator so there will be no field
current.
F+, F-
Field supply to the motor.
These terminals are used to provide feedback from the
motor armature terminals. This is required when the user
has a contactor in the main DC armature connection.
MA1, MA2
When the contactor is opened the drive will still be
receiving armature feedback. This allows the field
regulator to function correctly when the contactor is open.

Table 4-4 Line to line supply

Maximum nominal supply
Tolerance
Minimum nominal supply
Tolerance
Each drive has an onboard field controller with the following current
ratings.

Table 4-5 Current ratings

current
rating
A
MP25A4(R)
22
MP45A4(R)
40
MP75A4(R)
67
MP105A4(R) MP105A5(R)
94
MP155A4(R) MP155A5(R)
139
MP210A4(R) MP210A5(R)
188
MP350A4(R) MP350A5(R) MP350A6(R)
313
MP420A4(R)
375
MP470A5(R) MP470A6(R)
420
MP550A4(R)
492
MP700A4(R) MP700A5(R) MP700A6(R)
626
MP825A4(R) MP825A5(R) MP825A6(R)
738
MP900A4(R)
805
MP1200A4
MP1850A4
1073
MP1200A4R
MP1200A5R MP1200A6R
1654
MP1850A4R
MP1850A5R MP1850A6R
4.4.2
Supply requirements
Maximum supply in-balance: 2% negative phase sequence (equivalent
to 3% voltage in-balance between phases)
Frequency range: 48 to 65 Hz (maximum rate of frequency change is
7Hz/s)
4.5

Control 24Vdc supply

The 24Vdc input has three main functions.
It can be used to supplement the drive's own internal 24V when
multiple SM-Universal Encoder Plus, SM-Encoder Output Plus, SM-
I/O Plus, or SM-I/O 32 modules are being used and the current
drawn by these modules is greater than the drive can supply. (If too
much current is drawn from the drive, the drive will initiate a 'PS.24V'
trip)
Onboard
Advanced
Technical
PLC
parameters
data
Function
Specification
Maximum
auxiliary
Model
supply input
MP25A5(R)
MP45A5(R)
MP75A5(R)
MP1200A5
MP1200A6
MP1850A5
MP1850A6
UL
Diagnostics
information
Value
480V
+10%
208V
-10%
Maximum
continuous
field current
current
rating
A