Cable And Fuse Size Ratings; Table 12-10 Overall Drive Weights; Table 12-11 Typical Cable Sizes For Size 1 Drives - Emerson MP25A4 User Manual

Mentor mp series high performance dc drive 25a to 7400a, 480v to 690v two or four quadrant operation
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
information
Installation
Table 12-9 Acoustic noise data
Model
MP25A4(R)
MP25A5(R)
MP45A4(R)
MP45A5(R)
MP75A4(R)
MP75A5(R)
MP105A4(R)
MP105A5(R)
MP155A4(R)
MP155A5(R)
MP210A4(R)
MP210A5(R)
MP350A4(R)
MP350A5(R)
MP420A4(R)
MP470A5(R)
MP550A4(R)
MP700A4(R)
MP700A5(R)
MP825A4(R)
MP825A5(R)
MP900A4(R)
MP1200A4
MP1200A5
MP1850A4
MP1850A5
MP1200A4R
MP1200A5R
MP1850A4R
MP1850A5R
NOTE
* The acoustic noise figure for frame sizes 2C and 2D has been taken
with the bottom right angle ducting removed.
12.1.21
Overall dimensions
Refer to section 3.4 Mounting method on page 17.
12.1.22
Weights

Table 12-10 Overall drive weights

Model
MP25A4
MP25A5
MP45A4
MP45A5
MP75A4
MP75A5
MP25A4R
MP25A5R
MP45A4R
MP45A5R
MP75A4R
MP75A5R
MP105A4
MP105A5
MP155A4
MP155A5
MP210A4
MP210A5
MP105A4R
MP105A5R
MP155A4R
MP155A5R
MP210A4R
MP210A5R
MP350A4
MP350A5
MP420A4
MP470A5
MP550A4
MP350A4R
MP350A5R
MP420A4R
MP470A5R
MP550A4R
MP700A4
MP700A5
MP825A4
MP825A5
MP900A4
MP700A4R
MP700A5R
MP825A4R
MP825A5R
MP900A4R
MP1200A4
MP1200A5
MP1850A4
MP1850A5
MP1200A4R
MP1200A5R
MP1850A4R
MP1850A5R
Mentor MP User Guide
Issue: 3
Electrical
Getting
Basic
Running the
installation
started
parameters
Frame
SPL at 1m
Size
(dBA)
No fans
1A
installed
1B
MP350A6(R)
MP470A6(R)
2A
MP700A6(R)
MP825A6(R)
2B
MP1200A6
2C
MP1850A6
67*
MP1200A6R
2D
MP1850A6R
Frame
kg
size
10
10.1
1A
10.2
10.5
12.6
1B
13.0
MP350A6
35
MP470A6
2A
MP350A6R
38
MP470A6R
MP700A6
MP825A6
41
2B
MP700A6R
MP825A6R
46
MP1200A6
2C
100
MP1850A6
MP1200A6R
2D
138
MP1850A6R
www.controltechniques.com
SMARTCARD
Optimization
motor
operation
12.2

Cable and fuse size ratings

The selection of the correct fuse is essential to ensure the
safety of the installation
43
WARNING
Maximum continuous input currents are given in section 2.1 Ratings on
56
page 6 to aid the selection of fuses and cabling. The maximum input
current is dependent on the ripple content of the output current. A value
of 100% ripple has been assumed for the given ratings.
The cable sizing selected when installing a Mentor MP must comply with
the local wiring regulations. The information provided in this section is
68
provided for guidance purposes only.
The power terminals on Mentor MP frame size 1 drives have been
designed to accommodate a maximum cable size of 150mm
with a temperature of 90°C (194°F).
The power terminals on Mentor MP frame size 2A drives have been
designed to accommodate a maximum cable size of 2 x 150mm
350kcmil) with a temperature of 75°C (167°F).
The power terminals on Mentor MP frame size 2B drives have been
designed to accommodate 2 x 240mm
(194°F). The use of cables sized using the US national electrical code as
shown in Table 12-13 requires the use of a terminal adaptor.
The power terminals on Mentor MP frame size 2C and 2D drives have
been designed for use with busbars. The drive can be used with cables
as shown in Table 12-13 with the use of a terminal adaptor.
The actual cable size depends on a number of factors including:
Actual maximum continuous current
Ib
Ambient temperature
Cable support, method and grouping
22
Cable voltage drop
22.3
In applications where the motor used is of a reduced rating, the cable
sizing selected can be appropriate for that motor. To protect the motor
22.5
and the output cabling the drive must be programmed with the correct
motor rated current.
23.1
NOTE
27.8
When using reduced cable sizes, the branch circuit protection fuse rating
needs to be reduced in line with the cable size selected.
The following table shows typical cable sizes based on USA and
International standards, assuming 3 conductors per raceway/conduit, an
28.7
ambient temperature of 40°C (104°F) and applications with high output
current ripple content.

Table 12-11 Typical cable sizes for size 1 drives

77.2
Model
MP25A4(R)
MP25A5(R)
MP45A4(R)
MP45A5(R)
83.8
MP75A4(R)
MP75A5(R)
MP105A4(R)
MP105A5(R)
MP155A4(R)
MP155A5(R)
90.4
MP210A4(R)
MP210A5(R)
NOTE
101.4
1. The maximum cable size is defined by the power terminal housing
using 90°C (194°F) rated cables as per Table A.52-5 of the standard.
2. Assumes the use of 75°C rated cables, as per Table 310.16 of the
220.5
National Electrical Code.
The use of higher temperature rated cable would allow a reduction on
304.2
the minimum recommended cable size for Mentor MP shown above. For
high temperature cable sizing, please contact the supplier of the drive.
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
2
with a temperature of 90°C
[1]
IEC 60364-5-52
Input
Output
Input
2
2
8 AWG
2.5mm
4mm
2
2
4 AWG
10mm
10mm
2
2
1 AWG
16mm
25mm
2
2
1/0 AWG 1/0 AWG
25mm
35mm
2
2
3/0 AWG 4/0 AWG
50mm
70mm
2
2
300kcmil
95mm
95mm
UL
information
2
(350kcmil)
2
(2 x
[2]
UL508C/NEC
Output
8 AWG
4 AWG
1/0 AWG
350kcmil
151