3.3

Terminal cover removal

Isolation device
The AC supply must be disconnected from the drive using an
approved isolation device before any cover is removed from
the drive or before any servicing work is performed.
WARNING
Stored charge
The drive contains capacitors that remain charged to a
potentially lethal voltage after the AC supply has been
disconnected. If the drive has been energized, the AC
WARNING
supply must be isolated at least ten minutes before work
may continue.
3.3.1
Removing the terminal covers
The drive is installed with one control terminal cover.

Figure 3-1 Removing the control terminal cover (size 1 shown)

To remove the terminal cover, undo the screw and slide the terminal cover downwards.
When replacing the terminal covers the screw should be tightened with a maximum torque of 1 Nm (0.7 Ib ft).
3.3.2
Removing the finger-guard and break-outs

Figure 3-2 Removing the finger-guard break-outs

1
All sizes
Place finger-guard on a flat solid surface and hit relevant break-outs with
hammer as shown (1). Continue until all required break-outs are removed
(2). Remove any flash / sharp edges once the break-outs are removed.
14
Electrical
Getting
Basic
installation
started
parameters
2
www.controltechniques.com
Running the
SMARTCARD
Optimization
motor
operation
Pozi Pz2
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
Mentor MP User Guide
UL
information
Issue: 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents