Emerson MP25A4 User Manual page 71

Mentor mp series high performance dc drive 25a to 7400a, 480v to 690v two or four quadrant operation
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
information
Installation
Fb06
Drive encoder supply voltage
{0.76, 3.36}
RW
Txt
5V (0), 8V (1), 15V (2), 24V (3)
The encoder supply voltage present on the drive encoder connector is
defined by this parameter as 0 (5V), 1 (8V), 2 (15V) or 3 (24V)
Fb07
Drive encoder type
{0.77, 3.38}
RW
Txt
Ab (0), Fd (1), Fr (2)
The following encoders can be connected to the drive encoder port.
0, Ab: Quadrature incremental encoder, with or without marker pulse.
1, Fd: Incremental encoder with frequency and direction outputs, with or
without marker pulse.
2, Fr: Incremental encoder with forward and reverse outputs, with or
without marker pulse.
Fb08
Drive encoder termination select
{0.78, 3.39}
RW
Uni
0 to 2
The terminations may be enabled/disabled by this parameter as follows:
Encoder
Fb08
input
{0.78, 3.39} = 0
A-A\
Disabled
B-B\
Disabled
Z-Z\
Disabled
Fb09
Drive encoder speed feedback
{0.79, 3.27}
RW
Bi
FI
±10,000.0 rpm
Provided the set-up parameters for the drive encoder are correct this
parameter shows the encoder speed in rpm.
It should be noted that the value shown by this parameter is measured
over a 16ms sliding window period (in the same way as di05 (Pr 0.40,
3.02)), and so the ripple in this parameter accessible via comms or by an
option module is as defined for di05 (Pr 0.40, 3.02). The FI attribute for
this parameter is set, and so further filtering is applied when this
parameter is viewed with one of the drive keypads.
6.1.9
I/O
in01
Analog input 3 mode
{0.81, 7.15}
RW
Txt
0-20 (0), 20-0 (1), 4-20.tr (2),
20-4.tr (3), 4-20 (4), 20-4 (5),
VOLt (6), th.SC (7), th (8), th.
diSp (9)
The following modes are available for the analog input 3. A current loop
loss trip is generated if the input current falls below 3mA. In modes 4 and
5 the analog input level goes to 0.0% if the input current falls below 3mA.
Mentor MP User Guide
Issue: 3
Electrical
Getting
Basic
installation
started
parameters
US
5V (0)
US
Ab (0)
US
1
Fb08
Fb08
{0.78, 3.39} = 1
{0.78, 3.39} = 2
Enabled
Enabled
Enabled
Enabled
Disabled
Enabled
NC
PT
US
US
Eur: th (8), USA: VOLt (6)
www.controltechniques.com
Running the
SMARTCARD
Optimization
motor
operation
Parameter
Parameter
value
string
0
0-20
1
20-0
2
4-20.tr
3
20-4.tr
4
4-20
5
20-4
6
VOLt
7
th.SC
8
9
th.diSp
In modes 2 and 4 the destination parameter is at a value equivalent to
0.0% when the input current is less than 4mA. In modes 3 and 5 the
destination parameter is at a value equivalent to 100.0% when the input
current is less than 4mA.
in02
Analog input 1
{0.82, 7.01}
RO
Bi
±100.00 %
in03
Analog input 2
{0.83, 7.02}
RO
Bi
±100.0 %
in04
Analog input 3
{0.84, 7.03}
RO
Bi
±100.0 %
When analog input 3 is in thermistor mode the display indicates the
resistance of the thermistor as a percentage of 10kΩ.
in05
T24 digital I/O 1 state
{0.85, 8.01}
in06
T25 digital I/O 2 state
{0.86, 8.02}
in07
T26 digital I/O 3 state
{0.87, 8.03}
in08
T27 digital input 4 state
{0.88, 8.04}
in09
T28 digital input 5 state
{0.89, 8.05}
in10
T29 digital input 6 state
{0.90, 8.06}
RO
Bit
OFF (0) or On (1)
OFF (0) = Terminal inactive
On (1) = Terminal active
Onboard
Advanced
Technical
PLC
parameters
data
Mode
0 - 20mA
20 - 0mA
4 -20mA with trip on
loss
20 - 4mA with trip on
loss
4 - 20mA with no trip
on loss
20 - 4mA with no trip
on loss
Voltage mode
Thermistor with short
circuit detection
Thermistor without
th
short circuit detection
Thermistor display
only with no trip
NC
NC
NC
NC
UL
Diagnostics
information
Comments
Trip if I < 3mA
Trip if I < 3mA
0.0% if I < 4mA
TH trip if R > 3k3
TH reset if R < 1k8
THS trip if R < 50R
TH trip if R > 3k3
TH reset if R < 1k8
PT
PT
PT
PT
71