3.4.2 Grid supply and compressor wiring

Figure 4 shows the general wiring to the power grid and to the compressor. This wiring diagram
does not show any system-related components like fuse breaker, RCD and the additional ferrites for
EMC.
Paragraph 3.4.6
"Control
high-pressure limiter and the RS485 serial communication (Modbus
Figure 4: Wiring EV3185B, EV3150B

3.4.3 DC chokes

The integrated DC choke has protection class IP00 and temperature class H. The choke is positioned
between the heatsink of the drive and the drilled metal sheet, within the lower metal case. The fan
provides the necessary airstream for proper cooling. The chokes are fully covered to protect against
direct touching. Short connecting cables are used to minimize the possibility of EMI issues. The
choke dimensions are shown in Appendix 2: "Choke dimensions".
Drive model
Choke model
EV3185B
LE105-5002
EV3015B
R4002RJ
Safety protection: IP00, Class 0 / Temperature class: H
Table 8: DC chokes

3.4.4 Power grid connection

Table 9 includes information on how to connect the drive to the grid. The maximum input current is
based on a power factor of approximately 0.9. The ferrites, fuses and cable cross sections should be
considered as a recommendation and can be different based on the system design. The connection
between the cables and the drive screw terminals should be done with 5 mm ring terminals. The
drives are IP20 protection class; therefore, make sure to re-screw the terminal protection after wiring
the drive in order to maintain the standard. Also, the use of isolated ring and isolated blade terminals
is mandatory for all terminals to maintain the IP20 class.
Power grid
Drive model / choke
EV3185B
1 x DC choke
EV3150B
1 x DC choke
1)
Based on: DIN VDE 0298-4 (conductor temperature 90°C, laying method E)
Table 9: Connection to the input power grid
The grid must provide a R
each phase to be in line with standard EN 61000-3-12.
8
terminal" shows how to wire control-related components like DLT-sensor,
Number of
chokes
1 x DC
1 x DC
3-Phase grid: 400 VAC 50/60 Hz (L1, L2, L3, PE)
Fuse or circuit
Max input
breaker [A]
current [A]
@ 30°C
50
38
Type B
32
27
Type B
≥ 250 Ω, together with a system input current greater than 16 A on
SCE
®
) to the drive.
Electrical parameters
2 mH ± 10%, 50 A
2 mH ± 10%, 40 A
Cable cross
Usable Ferrite(s) to
1)
section [mm²]
reduce EMC noise
@ 60°C ambient
H63x38x25 KH10
10
(3 turns)
H63x38-25 KH10
6
(3 turns)
AGL_Sol_EV3_E_Rev_01