2.2.9

Certification

2–14
Standard
GE Multilin
Temperature Cycling
IEC 60068-2-38
Composite Temperature/Humidity
IEC 60255-5
Dielectric Strength
IEC 60255-5
Impulse Voltage
IEC 60255-5
Insulation Resistance
IEC 60255-21-1
Sinusoidal Vibration
IEC 60255-22-1
Damped Oscillatory Burst, 1 MHz
IEC 60255-22-2
Electrostatic Discharge: Direct
IEC 60255-22-3
Radiated RF Immunity
IEC 60255-22-4
Electrical Fast Transient / Burst Immunity
IEC 60255-22-5
Surge Immunity
IEC 60255-22-6
Conducted RF Immunity, 150 kHz to 80 MHz
IEC 60255-25
Radiated RF Emission
IEC 60255-25
Conducted RF Emission
IEC 60529
Ingress of Solid Objects and Water (IP)
IEC 61000-4-11
Voltage Dip; Voltage Interruption
IEEE C37.90.1
Fast Transient SWC
IEEE C37.90.1
Oscillatory Transient SWC
IEEE C37.90.3
Electrostatic Discharge: Air and Direct
PRODUCTION TESTS
Thermal cycling: .............................................operational test at ambient, reducing to –40°C and then
Dielectric strength: .......................................1.9 kV AC for 1 second, or 1.6 kV AC for 1 minute, per UL
DO NOT CONNECT FILTER GROUND TO SAFETY GROUND DURING ANY PRODUCTION
TESTS!
CERTIFICATION
ACA:.......................................................................conforms to RF emissions for Australia, tick mark
CE:..........................................................................conforms to EN 55011/CISPR 11, EN 50082-2
EN: .........................................................................EN50263 EMC - CE for Europe
FCC: .......................................................................conforms to RF emissions for North America, part 15
IEC:.........................................................................conforms to 1010-1, LVD - CE for Europe
ISO: ........................................................................Manufactured under an ISO9001 registered system.
UL:..........................................................................UL listed E83849 for the USA and Canada
CHAPTER 2: INTRODUCTION
Test Name
increasing to 60°C
508.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Level
–50°C / +80°C
65/–10°C at 93% RH
2300 V AC
5 kV
>100 MΩ / 500 V AC / 10 s
2 g
2.5 kV / 1 kV
8 kV
10 V/m
4 kV
4 kV / 2 kV
10 V/m
Group 1 Class A
Group 1 Class A
IP40 (front), IP20 (back)
0%, 40%, 100%
±4 kV
±2.5 kV
15 kV / 8 kV

Advertisement