GE 469 Instruction Manual page 284

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

Acceleration Trip
Analog I/P 2 Trip
Differential Trip
General Sw.D Trip
Load Shed Trip
Phase Reversal Trip
Remote Trip
RTD 3 Trip
RTD 7 Trip
RTD 11 Trip
Single Phasing
(Unbalanced)
6–34
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The event recorder stores motor and system information each time an event occurs. An
event description is stored along with a time and date stamp for troubleshooting purposes.
Events include all trips, any alarm optionally (except Service Alarm, and 469 Not Inserted
Alarm, which always records as events), loss of control power, application of control power,
emergency restarts, and motor starts when a blocking function is active. The latter event
could occur if the block start contacts were shorted out to bypass the 469 and start the
motor.
is the most recent event and
EVENT 01
bumps the other event records up one until
is lost when a new event occurs. This information can be cleared using the
EVENT 256
SETUP
CLEAR DATA
Table 6–3: Cause of Events (Sheet 1 of 2)
Analog Diff 1-2 Trip
Analog I/P 3 Trip
General Sw.A Trip
Ground Fault Backup
Mechanical Jam Trip
Power Factor Trip
Reverse Power Trip
RTD 4 Trip
RTD 8 Trip
RTD 12 Trip
Speed Switch Trip
POWER FACTOR
EVENT01: 0.00
TORQUE
EVENT01: 0.0 Nm
ANALOG I/P 1
EVENT01: 0 Units
ANALOG I/P 2
EVENT01: 0 Units
ANALOG I/P 3
EVENT01: 0 Units
ANALOG I/P 4
EVENT01: 0 Units
is the oldest event. Each new event
EVENT 256
EVENT 256
settings.
CLEAR EVENT RECORD
TRIPS
Analog Diff 3-4 Trip
Analog I/P 4 Trip
General Sw.B Trip
Ground Fault Trip
Overload Trip
Pressure Sw. Trip
RTD 1 Trip
RTD 5 Trip
RTD 9 Trip
Short Circuit Backup
Tachometer Trip
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
Range: 0.01 to 0.99 Lead or Lag, 0.00,
1.00 Not seen if VT Connection
is set as None.
Range: 0 to 999999.9. Seen only if
Torque Metering is Enabled
Range: –50000 to 50000. Not seen if
Analog Input 1 is Disabled.
Range: –50000 to 50000. Not seen if
Analog Input 2 is Disabled.
Range: –50000 to 50000. Not seen if
Analog Input 3 is Disabled.
Range: –50000 to 50000. Not seen if
Analog Input 4 is Disabled.
is reached. The event record in
Analog I/P 1 Trip
Current U/B Trip
General Sw.C Trip
Incomplete Seq Trip
Overvoltage Trip
Reactive Power Trip
RTD 2 Trip
RTD 6 Trip
RTD 10 Trip
Short Circuit Trip
Undercurrent Trip
S1 469