GE 469 Instruction Manual page 154

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

COMMUNICATIONS
5–12
The following settings appear when the relay is ordered with the DeviceNet (D) option.
PATH: SETTINGS
S1 469 SETUP
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Enter the dedicated MAC ID and baud rate as per the DeviceNet design (Refer to GEK-
106491C: 469 Communications Guide). The DeviceNet option is implemented by the 469
relay using the AnyBus-S DeviceNet (HMS) module as a communication adapter. The
module is ODVA certified and acts as a server between the relay and the DeviceNet
network.
The following master/slave connection objects are supported by the 469 DeviceNet
implementation:
• Explicit Messaging Connection
• Poll I/O Connection
• Change of State or Cyclic I/O Connection
The following objects have been implemented:
Identity object
Message Router object
DeviceNet object
Assembly object
Connection object
Acknowledge Handler object
I/O Data Input Mapping object
Parameter Data Input Mapping object
Refer to publication GEK-106491C: 469 Communications Guide for additional details
on the DeviceNet implementation.
COMMUNICATIONS
SLAVE ADDRESS:
254
COMPUTER RS485
BAUD RATE: 9600
COMPUTER RS485
PARITY: None
FRONT PORT RS232
BAUD RATE: 19200
DEVICENET MAC ID:
1
DEVICENET
BAUD RATE: 125K
Object
DeviceNet objects
469 specific objects
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: 1 to 254 in steps of 1
Range: 300, 1200, 2400, 4800, 9600,
19200
Range: None, Odd, Even
Range: 300, 1200, 2400, 4800, 9600,
19200
Range: 0 to 63
Range: 125K, 250K, 500K
Class
01h
02h
03h
04h
05h
2Bh
A0h
B0h