CHAPTER 5: SETTINGS
ASSIGNABLE
ASSIGNABLE
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Vibration Switch Alarm
PATH: SETTINGS
S3 DIGITAL INPUTS
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
These settings apply only if the
Once the Vibration Switch Alarm function is chosen for one of the digital inputs, the
settings messages shown follow the assignment message. When the motor is stopped or
running, the digital input will be monitored. If a closure occurs, an alarm will occur after the
specified delay.
Vibration Switch Trip
PATH: SETTINGS
S3 DIGITAL INPUTS
[
MESSAGE
MESSAGE
These settings apply only if the
Once Vibration Switch Trip is chosen for a digital input, the settings shown follow the
assignment message. When the motor is stopped or running, the digital input will be
monitored. If a closure occurs, a trip will occur after the specified delay.
ASSIGNABLE INPUT 1(4)
INPUT 1 FUNCTION:
Vibration Sw
VIBRATION SWITCH
ALARM: Unlatched
ASSIGN ALARM
RELAYS:
VIBRATION SW.
ALARM
VIBRATION SW.
ALARM
is "Vibration Sw. Alarm".
INPUT 1(4) FUNCTION
ASSIGNABLE INPUT 1(4)
INPUT 1 FUNCTION:
Vibration Sw Trip
ASSIGN TRIP
RELAYS:
VIBRATION SW.
TRIP
is "Pressure Sw. Trip".
INPUT 1(4) FUNCTION
Range: See above
Range: Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 0.1 to 100.0 s in steps of 0.1
Range: On, Off
Range: See above
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 0.1 to 100.0 s in steps of 0.1
5–29