OVERLOAD
5–46
Voltage Dependent Overload Curves
If the
SELECT CURVE STYLE
following settings will appear:
PATH: SETTINGS
S5 THERMAL MODEL
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
is set to "Voltage Dependent" in the Thermal Model, the
OVERLOAD CURVE SETUP
TIME TO TRIP AT
1.01 x FLA:
TIME TO TRIP AT
1.05 x FLA:
TIME TO TRIP AT
1.10 x FLA:
TIME TO TRIP AT
1.20 x FLA: 795.4
TIME TO TRIP AT
1.30 x FLA: 507.2
TIME TO TRIP AT
1.40 x FLA: 364.6
TIME TO TRIP AT
1.50 x FLA: 280.0
TIME TO TRIP AT
1.75 x FLA: 169.7
TIME TO TRIP AT
2.00 x FLA: 116.6
TIME TO TRIP AT
2.25 x FLA: 86.1
TIME TO TRIP AT
2.50 x FLA: 66.6
TIME TO TRIP AT
2.75 x FLA: 53.3
TIME TO TRIP AT
3.00 x FLA: 43.7
TIME TO TRIP AT
3.25 x FLA: 36.6
TIME TO TRIP AT
3.50 x FLA: 31.1
TIME TO TRIP AT
3.75 x FLA: 26.8
TIME TO TRIP AT
4.00 x FLA: 23.3
TIME TO TRIP AT
4.25 x FLA: 20.5
TIME TO TRIP AT
4.50 x FLA: 18.2
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1