GE 469 Instruction Manual page 174

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

ASSIGNABLE
ASSIGNABLE
5–32
General Switch A to D
PATH: SETTINGS
S3 DIGITAL INPUTS
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
These settings apply only if the
appear for General Switches B, C, and D.
There are four general switch functions assignable to the four digital inputs. Once a
general switch function is chosen for one of the digital inputs, the settings messages
shown here follow the assignment message. An alarm and/or trip may then be configured
for that input. The alarm and/or trip may be assigned a common name and a common
block time from motor start if required (if the alarm is to be disabled until some period of
time after he motor has been started). A value of "0" for the
that the feature is always active, when the motor is stopped or running. The switch may
also be defined as normally open or normally closed. After the block delay has expired, the
digital input will be monitored. If the switch is not in its normal state after the specified
delay, an alarm or trip will occur.
Capture Trace
PATH: SETTINGS
S3 DIGITAL INPUTS
[
ASSIGNABLE INPUT 1(4
INPUT 1 FUNCTION:
General Sw. A
SWITCH NAME:
General Sw. A
GENERAL SWITCH A:
Normally Open
BLOCK INPUT
FROM START: 0 s
GENERAL SWITCH A
ALARM: Off
ASSIGN ALARM
RELAYS:
GENERAL SWITCH A
ALARM DELAY: 5.0
GENERAL SWITCH A
EVENTS: Off
GENERAL SWITCH A
TRIP: Off
ASSIGN TRIP
RELAYS:
GENERAL SWITCH A
TRIP DELAY: 5.0 s
is "General Switch A". Similar messages
INPUT 1(4) FUNCTION
ASSIGNABLE INPUT 1(4)
INPUT 1 FUNCTION:
Capture Trace
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
)
Range: See above
Range: 12 alphanumeric characters
Range: Normally Open,
Normally Closed.
Range: 0 to 5000 s in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 0.1 to 5000.0 s in steps of 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 0.1 to 5000.0 s in steps of 0.1
settings indicates
BLOCK TIME
Range: See above.

Advertisement

Table of Contents
loading

Table of Contents