GE 469 Instruction Manual page 168

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

ASSIGNABLE
ASSIGNABLE
5–26
There are four (4) user-assignable digital inputs configurable to a number of different
functions (see below), or turned Off. Once a function is chosen, any messages that follow
may be used to set pertinent parameters for operation. Each function may only be chosen
once. Assignable Inputs 1 to 4 are activated by shorting D19 to D22 (respectively) with D23.
The range for the
INPUT 1(4) FUNCTION
Switch Trip, Load Shed Trip, Pressure Sw Alarm, Pressure Switch Trip, Vibration Sw Alarm,
Vibration Sw Trip, Digital Counter, Tachometer, General Sw A, General Sw B, General Sw C,
General Sw D, Capture Trace, Simulate Pre-Fault, Simulate Fault, Simulate Pre Fault... Fault.
Two-speed motor protection is enabled with the
ENABLE 2-SPEED MOTOR PROTECTION
Assignable Input 4 is dedicated as the two-speed motor monitor and terminals D22 and
D23 are monitored for a contact closure. Closure of the contact signifies that the motor is
in Speed 2 or High Speed. If the input is open, it signifies that the motor is in Speed 1. This
allows the 469 to determine which settings should be active at any given point in time.
Remote Alarm
PATH: SETTINGS
S3 DIGITAL INPUTS
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
These settings apply only if the
Once the Remote Alarm function is chosen for one of the assignable digital inputs, the
settings messages shown here will follow the assignment message. An alarm relay may be
selected and the name of the alarm may be altered. A contact closure on the digital input
assigned as Remote Alarm will cause an alarm within 100 ms with the name that has been
chosen. Multiple sources may be used to trigger a remote alarm by paralleling inputs (see
FIGURE 5–4: Remote Alarm/Trip from Multiple Sources on page 5–27).
Remote Trip
PATH: SETTINGS
S3 DIGITAL INPUTS
[
MESSAGE
MESSAGE
settings is: Off, Remote Alarm, Remote Trip, Speed
S2 SYSTEM SETUP
settings. If the two-speed motor feature is enabled,
ASSIGNABLE INPUT 1(4)
INPUT 1 FUNCTION:
Remote Alarm
REMOTE ALARM
NAME:
REMOTE
ALARM: Unlatched
ASSIGN ALARM
RELAYS:
REMOTE ALARM
EVENTS: Off
is "Remote Alarm".
INPUT 1(4) FUNCTION
ASSIGNABLE INPUT 1(4)
INPUT 1 FUNCTION:
Remote Trip
REMOTE TRIP NAME:
Remote Trip
ASSIGN TRIP
RELAYS:
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
CURRENT SENSING
Range: See above
Range: 20 alphanumeric characters
Range: Latched, Unlatched
Range: Alarm, Alarm & Aux2, Alarm &
Aux2 & Aux3, Alarm & Aux3,
Auxiliary2
Range: On, Off
Range: See above
Range: 20 character alphanumeric
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3