CHAPTER 5: SETTINGS

5.14.4 Test Output Relays

TEST

5.14.5 Test Analog Outputs

TEST
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
PATH: SETTINGS
S13 469 TESTING
[
In addition to the simulation modes, the
during startup or testing to verify that the output relays are functioning correctly.
The output relays can only be forced to operate only if the motor is stopped and there are
no trips, alarms, or start blocks active. If any relay is forced to operate, the relay will toggle
from its normal state when there are no trips, alarms, or blocks to its active state. The
appropriate relay indicator will illuminate at that time. Selecting "Disabled" places the
output relays back in service. If the 469 measures phase current or control power is cycled,
the
FORCE OPERATION OF RELAYS
output relays will revert back to their normal states.
If any relay is forced, the 469 In Service LED will flash, indicating that the 469 is not in
protection mode.
PATH: SETTINGS
S13 469 TESTING
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
In addition to the simulation modes, the
during startup or testing to verify that the analog outputs are functioning correctly.
The analog outputs can only be forced if the motor is stopped and there are no trips,
alarms, or start blocks active. When the
the output reflects the forced value as a percentage of the 4 to 20 mA or 0 to 1 mA range.
Selecting "Disabled" places all four analog output channels back in service, reflecting the
parameters programmed to each. If the 469 measures phase current or control power is
cycled, the
FORCE ANALOG OUTPUTS FUNCTION
outputs revert back to their normal state.
Any time the analog outputs are forced, the 469 In Service LED will flash, indicating that the
469 is not in protection mode.
TEST OUTPUT RELAYS
FORCE OPERATION
OF
TEST OUTPUT RELAYS
settings will automatically become disabled and the
TEST ANALOG OUTPUT
FORCE ANALOG OUT-
PUTS
ANALOG OUTPUT 1
FORCED VALUE: 0%
ANALOG OUTPUT 2
FORCED VALUE: 0%
ANALOG OUTPUT 3
FORCED VALUE: 0%
ANALOG OUTPUT 4
FORCED VALUE: 0%
TEST ANALOG OUTPUT
FORCE ANALOG OUTPUTS FUNCTION
is automatically disabled and all analog
Range: Disabled, 1 Trip, 2 Auxiliary,
3 Auxiliary, 4 Alarm, 5 Block,
6 Service, All Relays, No Relays
settings group may be used
Range: Enabled, Disabled
Range: 0 to 100%, step 1
Range: 0 to 100%, step 1
Range: 0 to 100%, step 1
Range: 0 to 100%, step 1
settings group may be used
is "Enabled",
5–101