GE 469 Instruction Manual page 215

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
5.9.4
RTD 11
#11
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
RTDs 7 through 10 default to "Bearing" RTD type. There are individual alarm and trip
configurations for each RTD. This allows one of the RTDs to be turned off if it malfunctions.
The alarm level, high alarm level and the trip level are normally set slightly above the
normal running temperature, but below the bearing temperature rating. Trip voting has
been added for extra reliability in the event of RTD malfunction. If enabled, a second RTD
must also exceed the trip temperature of the RTD being checked before a trip will be
issued. If the RTD is chosen to vote with itself, the voting feature is disabled. Each RTD
name may be changed if desired.
PATH: SETTINGS
S8 RTD TEMPERATURE
RTD
[ ]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
RTD 11 defaults to "Other" RTD type. The Other selection allows the RTD to be used to
monitor any temperature that might be required, either for a process or additional
bearings or other. There are individual alarm, high alarm and trip configurations for this
RTD #11
RTD #11 APPLICA-
TION:
RTD #11 NAME:
RTD #11 ALARM:
Off
ASSIGN ALARM
RELAYS:
RTD #11 ALARM
TEMPERATURE: 80°C
RTD #7 HIGH
ALARM:
HIGH ALARM
RELAYS:
RTD #11 HIGH
ALARM
RTD #11 ALARM
EVENTS: Off
RTD #11 TRIP:
Off
RTD #11 TRIP VOT-
ING:
ASSIGN TRIP
RELAYS:
RTD #11 TRIP
TEMPERATURE: 90°C
Range: Stator, Bearing, Ambient, Other,
None
Range: 8 alphanumeric characters
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 250°C in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 250°C in steps of 1
Range: On, Off
Range: Off, Latched, Unlatched
Range: RTD #1 to RTD #12
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 1 to 250°C in steps of 1
5–73