5.11.2 Power Factor

POWER
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
PATH: SETTINGS
S10 POWER ELEMENTS
[
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
If the 469 is applied on a synchronous motor, it is desirable not to trip or alarm on power
factor until the field has been applied. Therefore, this feature can be blocked until the
motor comes up to speed and the field is applied. From that point forward, the power
factor trip and alarm elements will be active. Once the power factor is less than either the
Lead or Lag level, for the specified delay, a trip or alarm will occur indicating a Lead or Lag
condition. The power factor alarm can be used to detect loss of excitation and out of step.
POWER FACTOR
BLOCK PF ELEMENT
FROM START: 1 s
POWER FACTOR
ALARM: Off
ASSIGN ALARM
RELAYS:
POWER FACTOR LEAD
ALARM LEVEL: Off
POWER FACTOR LAG
ALARM LEVEL: Off
POWER FACTOR
ALARM
POWER FACTOR
ALARM
POWER FACTOR
TRIP: Off
ASSIGN TRIP
RELAYS:
POWER FACTOR LEAD
TRIP LEVEL: Off
POWER FACTOR LAG
TRIP LEVEL: Off
POWER FACTOR TRIP
DELAY: 1.0 s
Range: 0 to 5000 s in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 0.05 to 1.00 in steps of 0.01.
Enter 1.00 to turn feature off.
Range: 0.05 to 1.00 in steps of 0.01.
Enter 1.00 to turn feature off.
Range: 0.2 to 30.0 s in steps of 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 0.05 to 1.00 in steps of 0.01.
Enter 1.00 to turn feature off.
Range: 0.05 to 1.00 in steps of 0.01.
Enter 1.00 to turn feature off.
Range: 0.2 to 30.0 s in steps of 0.1